Assessment Year | 2016 |
---|---|
Principal Product | Products of Purchased Glass |
NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231: Glass Products, Made of Purchased Glass |
Sales Range | $50 M to 100M |
# of Employees | 192 |
Plant Area |
200,000
ft2
|
Annual Production | 300,000
pieces
|
Production Hrs. Annual | 5,200
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $80,043 | 2,054,317 |
kWh
|
$0.039 |
Electricity Demand | $111,338 | 7,267 |
kW-mo/yr
|
$15.32 |
Natural Gas | $35,811 | 4,597 |
MMBtu
|
$7.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,918 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,835 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,826 | $10,031 |
$5,154
132,145
kWh
|
$4,672
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,504 | $362 |
$2,884
73,938
kWh
|
$2,620
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,290 | $6,270 |
$2,778
71,243
kWh
|
$2,512
-
kW-mo/yr
|
- | |
04 | 2.6232: Install set-back timers | $3,716 | $4,223 | - | - |
$3,716
-
MMBtu
|
|
05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,568 | $1,114 | - | - |
$3,568
-
MMBtu
|
|
06 | 2.4224: Upgrade controls on compressors | $2,799 | $5,000 |
$1,466
37,585
kWh
|
$1,333
-
kW-mo/yr
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $1,575 | $4,088 |
$824
21,138
kWh
|
$751
-
kW-mo/yr
|
- | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $640 | $11 |
$334
8,568
kWh
|
$306
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $32,918 | $31,099 |
$13,440
344,617
kWh
|
$12,194
-
kW-mo/yr
|
$7,284
-
MMBtu
|
||
TOTAL IMPLEMENTED | $22,835 | $20,762 |
$11,974
307,032
kWh
|
$10,861
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs