Assessment Year | 2013 |
---|---|
Principal Product | entertainment services |
NAICS | 721120: Casino Hotels |
SIC | 7011: Hotels and Motels |
Sales Range | $50 M to 100M |
# of Employees | 1,600 |
Plant Area |
563,897
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,188,604 | 29,585,456 |
kWh
|
$0.040 |
Electricity Demand | $547,637 | 55,517 |
kW-mo/yr
|
$9.86 |
Natural Gas | $275,278 | 42,189 |
MMBtu
|
$6.52 |
Other Gas | $295,895 | 9,528 |
MMBtu
|
$31.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $261,565 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $70,424 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $80,805 | $74,600 |
$21,284
529,460
kWh
|
- |
$59,521
-
MMBtu
|
- | - | - | |
02 | 2.7496: Install partitions to reduce size of conditioned space | $62,278 | $279,714 |
$15,237
379,023
kWh
|
$5,443
-
kW-mo/yr
|
$41,598
-
MMBtu
|
- | - | - | |
03 | 2.3191: Use demand controller or load shedder | $29,974 | $21,000 | - |
$29,974
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.8122: Use utility controlled power management | $22,626 | $5,000 | - | - | - | - | $(-33,624.0) | $56,250 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,150 | $16,076 |
$9,812
244,091
kWh
|
$4,338
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $13,965 | $1,700 | - | - |
$10,595
-
MMBtu
|
$4,720
-
MMBtu
|
$(-1,350.0) | - | |
07 | 2.2222: Convert liquid heaters from underfiring to immersion or submersion heating | $13,558 | $23,000 |
$(-14,790.0)
(-367,920)
kWh
|
$(-4,969.0)
-
kW-mo/yr
|
- |
$33,317
-
MMBtu
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,352 | $13,858 |
$6,838
170,109
kWh
|
$2,514
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,383 | $7,846 |
$2,535
63,072
kWh
|
$848
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,008 | - |
$1,519
37,796
kWh
|
$1,489
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.7243: Improve air circulation with destratification fans / other methods | $2,308 | $8,400 | - | - |
$2,308
-
MMBtu
|
- | - | - | |
12 | 2.7261: Install timers and/or thermostats | $2,071 | $750 |
$1,548
38,500
kWh
|
$523
-
kW-mo/yr
|
- | - | - | - | |
13 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,869 | $1,152 | - | - |
$130
-
MMBtu
|
$1,739
-
MMBtu
|
- | - | |
14 | 2.2136: Install / repair insulation on steam lines | $1,243 | $1,168 | - | - |
$346
-
MMBtu
|
$897
-
MMBtu
|
- | - | |
15 | 2.4157: Establish a predictive maintenance program | $715 | $1,000 |
$1,183
29,423
kWh
|
$1,065
-
kW-mo/yr
|
- | - | $(-1,533.0) | - | |
16 | 2.4151: Develop a repair/replace policy | $260 | $160 |
$177
4,413
kWh
|
$158
-
kW-mo/yr
|
- | - | $(-75.0) | - | |
TOTAL RECOMMENDED | $261,565 | $455,424 |
$45,343
1,127,967
kWh
|
$41,383
-
kW-mo/yr
|
$114,498
-
MMBtu
|
$40,673
-
MMBtu
|
$(-36,582.0) | $56,250 | ||
TOTAL IMPLEMENTED | $70,424 | $46,382 |
$22,252
553,568
kWh
|
$9,712
-
kW-mo/yr
|
$10,725
-
MMBtu
|
$6,459
-
MMBtu
|
$(-34,974.0) | $56,250 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs