Assessment Year 2009
Principal Product Printed Books and Forms
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2759: Commercial Printing, Not Elsewhere Classified
Sales Range $1
M
to 5
M
# of Employees 400
Plant Area 180,000
ft2
Annual Production 40,000,000
lb
Production Hrs. Annual 8,760
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $358,018 6,377,640
kWh
Electricity Demand $88,023 13,197
kW-mo/yr
Electricity Fees $1,095 -
Natural Gas $26,224 2,080
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $58,361 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $43,626

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $19,773 $18,784 $16,645
296,483
kWh
$3,128
-
kW-mo/yr
- -
02 2.4239: Eliminate or reduce compressed air usage $10,132 $1,667 $8,711
155,164
kWh
$1,421
-
kW-mo/yr
- -
03 2.4239: Eliminate or reduce compressed air usage $5,526 $6,750 $4,946
88,104
kWh
$580
-
kW-mo/yr
- -
04 2.2437: Recover waste heat from equipment $5,525 $2,660 $310
5,526
kWh
$53
-
kW-mo/yr
$5,162
-
MMBtu
-
05 2.4157: Establish a predictive maintenance program $4,417 $1,000 $4,005
71,336
kWh
$654
-
kW-mo/yr
- $(-242.0)
06 2.4151: Develop a repair/replace policy $3,444 $681 $3,217
57,298
kWh
$527
-
kW-mo/yr
- $(-300.0)
07 2.7111: Reduce illumination to minimum necessary levels $3,252 $392 $2,798
39,735
kWh
$454
-
kW-mo/yr
- -
08 2.6231: Utilize controls to operate equipment only when needed $2,814 $5,000 $2,420
43,100
kWh
$394
-
kW-mo/yr
- -
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,192 - $1,885
33,575
kWh
$307
-
kW-mo/yr
- -
10 2.4221: Install compressor air intakes in coolest locations $870 $660 $750
13,367
kWh
$120
-
kW-mo/yr
- -
11 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $416 $283 $356
6,339
kWh
$60
-
kW-mo/yr
- -
TOTAL RECOMMENDED $58,361 $37,877 $46,043
810,027
kWh
$7,698
-
kW-mo/yr
$5,162
-
MMBtu
$(-542.0)
TOTAL IMPLEMENTED $43,626 $22,807 $37,617
659,930
kWh
$6,551
-
kW-mo/yr
- $(-542.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs