Assessment Year 2000
Principal Product Textile products
NAICS
n/a
SIC 2299: Textile goods, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 125
Plant Area 99,000
ft2
Annual Production 0
units
Production Hrs. Annual 2,210
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $27,407 686,694
kWh
Electricity Demand $31,238 1,743
kW-mo/yr
Natural Gas $20,754 2,878
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $46,959 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $13,561

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Solid Waste (non-haz) Savings Solid Waste (haz) Savings Administrative Changes Savings
01 2.6232: Install set-back timers $318 $28 $318
7,913
kWh
- - - -
02 2.4221: Install compressor air intakes in coolest locations $24 $62 $24
586
kWh
- - - -
03 2.4231: Reduce the pressure of compressed air to the minimum required $206 $15 $206
5,275
kWh
- - - -
04 2.7111: Reduce illumination to minimum necessary levels $270 $150 $270
6,741
kWh
- - - -
05 2.7144: Install spectral reflectors / delamp $3,746 $3,344 $3,746
30,774
kWh
- - - -
06 2.7122: Disconnect ballasts $5,102 $1,527 $5,102
48,652
kWh
- - - -
07 2.7243: Improve air circulation with destratification fans / other methods $3,937 - - $3,937
-
MMBtu
- - -
08 2.2515: Use optimum thickness insulation $73 $176 - $73
-
MMBtu
- - -
09 2.7142: Utilize higher efficiency lamps and/or ballasts $708 $693 $708
4,396
kWh
- - - -
10 2.6218: Turn off equipment when not in use $3,187 - $3,187
129,543
kWh
- - - -
11 3.5212: Regrind, reuse, or sell scrap plastic parts $44 - - - - $44
-
lb
-
12 3.5217: Reuse / recycle/ sell paper products $9,344 $336 - - $9,344
-
lb
- -
13 4.652: Replace existing equipment with more suitable substitutes $20,000 $6,000 - - - - $20,000
TOTAL RECOMMENDED $46,959 $12,331 $13,561
233,880
kWh
$4,010
-
MMBtu
$9,344
-
lb
$44
-
lb
$20,000
TOTAL IMPLEMENTED $13,561 $5,819 $13,561
233,880
kWh
- - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Solid Waste (non-haz) Savings Solid Waste (haz) Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs