Assessment Year | 2020 |
---|---|
Principal Product | Underground Construction Equipment |
NAICS | 333131: Mining Machinery and Equipment Manufacturing |
SIC | 3532: Mining Machinery and Equipment, Except Oil and Gas Field Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
136,500
ft2
|
Annual Production | 3,000
pieces
|
Production Hrs. Annual | 4,375
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $80,586 | 912,640 |
kWh
|
$0.088 | |
Electricity Demand | $22,138 | 2,992 |
kW-mo/yr
|
$7.40 | |
Electricity Fees | $108,921 | - |
|
- | |
Natural Gas | $26,830 | 4,462 |
MMBtu
|
$6.01 | |
Waste Disposal Costs | |||||
Water Usage | $2,661 | 165 |
Tgal
|
$16.12 | |
Water Disposal | $1,919 | 165 |
Tgal
|
$11.63 | |
TOTAL YEARLY COSTS | $243,055 | ||||
RECOMMENDED SAVINGS* | $42,920 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $726 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $26,709 | $110,788 |
$26,709
302,487
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,927 | $8,716 |
$6,568
74,378
kWh
|
$359
-
kW-mo/yr
|
- | |
03 | 2.7444: Close holes and openings in building such as broken windows | $2,335 | $1,700 | - | - |
$2,335
-
MMBtu
|
|
04 | 2.7232: Replace existing hvac unit with high efficiency model | $1,791 | $15,060 | - | - |
$1,791
-
MMBtu
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,761 | $3,855 |
$1,517
17,177
kWh
|
$244
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,679 | $1,750 |
$1,365
15,461
kWh
|
$314
-
kW-mo/yr
|
- | |
07 | 2.7134: Use photocell controls | $541 | $1,075 |
$541
6,127
kWh
|
- | - | |
08 | 2.7135: Install occupancy sensors | $451 | $750 |
$396
4,485
kWh
|
$55
-
kW-mo/yr
|
- | |
09 | 2.4221: Install compressor air intakes in coolest locations | $366 | $1,250 |
$297
3,373
kWh
|
$69
-
kW-mo/yr
|
- | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $360 | - |
$293
3,308
kWh
|
$67
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $42,920 | $144,944 |
$37,686
426,796
kWh
|
$1,108
-
kW-mo/yr
|
$4,126
-
MMBtu
|
||
TOTAL IMPLEMENTED | $726 | $1,250 |
$590
6,681
kWh
|
$136
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs