Assessment Year 1989
Principal Product TEXTILE FLOCK
NAICS
n/a
SIC 2299: Textile goods, Not Elsewhere Classified
Sales Range $5
M
to 10
M
# of Employees 80
Plant Area
n/a
Annual Production 1,250,000
lb
Production Hrs. Annual 6,000
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $52,878 719,519
kWh
Natural Gas $88,805 27,621
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $24,278 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $11,499

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.8113: Purchase gas directly from a contract gas supplier $4,188 - - $4,188
-
MMBtu
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $5,100 - $5,100
-
kWh
-
03 2.2414: Use waste heat from hot flue gases to preheat $4,040 $5,000 - $4,040
-
MMBtu
04 2.7261: Install timers and/or thermostats $2,536 $750 - $2,536
-
MMBtu
05 2.7142: Utilize higher efficiency lamps and/or ballasts $1,120 $1,270 $1,120
15,240
kWh
-
06 2.1233: Analyze flue gas for proper air/fuel ratio $1,671 $500 - $1,671
-
MMBtu
07 2.6218: Turn off equipment when not in use $1,540 $800 - $1,540
-
MMBtu
08 2.4221: Install compressor air intakes in coolest locations $825 $3,000 $825
11,137
kWh
-
09 2.1311: Replace electrically-operated equipment with fossil fuel equipment $686 $1,000 $844
11,430
kWh
$(-158.0)
-
MMBtu
10 2.4111: Utilize energy-efficient belts and other improved mechanisms $640 - $640
8,792
kWh
-
11 2.7447: Install vinyl strip / high speed / air curtain doors $1,500 $1,500 - $1,500
-
MMBtu
12 2.7494: Install storm windows and doors $432 $1,488 - $432
-
MMBtu
TOTAL RECOMMENDED $24,278 $15,308 $8,529
46,599
kWh
$15,749
-
MMBtu
TOTAL IMPLEMENTED $11,499 $4,008 $6,860
24,032
kWh
$4,639
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs