| Assessment Year | 2017 |
|---|---|
| Principal Product | Commercial Printing |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2754: Commercial Printing, Gravure |
| Sales Range | $5 M to 10M |
| # of Employees | 135 |
| Plant Area |
40,000
ft2
|
| Annual Production | 10,000,000
units
|
| Production Hrs. Annual | 3,640
hrs
|
| Location (State) | Kentucky |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $156,353 | 1,878,100 |
kWh
|
$0.083 | |
| Electricity Demand | $25,149 | 4,420 |
kW-mo/yr
|
$5.69 | |
| Electricity Fees | $360 | - |
|
- | |
| Natural Gas | $23,454 | 3,571 |
MMBtu
|
$6.57 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,427 | 477 |
Tgal
|
$5.09 | |
| Water Disposal | $2,246 | 477 |
Tgal
|
$4.71 | |
| TOTAL YEARLY COSTS | $209,989 | ||||
| RECOMMENDED SAVINGS* | $53,695 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $31,837 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7442: Keep doors and windows shut when not on use | $7,278 | - |
$6,653
80,154
kWh
|
$625
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,467 | $25,474 |
$15,901
191,575
kWh
|
$2,566
-
kW-mo/yr
|
- | - | |
| 03 | 2.7135: Install occupancy sensors | $1,276 | $952 |
$1,276
15,375
kWh
|
- | - | - | |
| 04 | 2.7134: Use photocell controls | $759 | $60 |
$759
9,145
kWh
|
- | - | - | |
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,260 | $750 | - | - | - |
$2,260
-
MMBtu
|
|
| 06 | 2.3212: Optimize plant power factor | $8,180 | $18,216 | - | - | $8,180 | - | |
| 07 | 2.4152: Use only certified motor repair shops | $1,143 | $3,928 |
$933
11,240
kWh
|
$210
-
kW-mo/yr
|
- | - | |
| 08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,080 | - |
$6,949
83,720
kWh
|
$131
-
kW-mo/yr
|
- | - | |
| 09 | 2.4322: Use or replace with energy efficient substitutes | $314 | $311 |
$314
3,781
kWh
|
- | - | - | |
| 10 | 2.4224: Upgrade controls on compressors | $2,600 | $5,000 |
$2,156
25,975
kWh
|
$444
-
kW-mo/yr
|
- | - | |
| 11 | 2.2437: Recover waste heat from equipment | $4,338 | $5,754 |
$2,250
27,115
kWh
|
$467
-
kW-mo/yr
|
- |
$1,621
-
MMBtu
|
|
| TOTAL RECOMMENDED | $53,695 | $60,445 |
$37,191
448,080
kWh
|
$4,443
-
kW-mo/yr
|
$8,180 |
$3,881
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $31,837 | $35,725 |
$27,992
337,245
kWh
|
$3,845
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs