Assessment Year | 2005 |
---|---|
Principal Product | Radio receivers |
NAICS | 334220: Radio and Television Broadcasting and Wireless Communications Equipment Manufacturing |
SIC | 3663: Radio and Television Broadcasting and Communications Equipment |
Sales Range | $10 M to 50M |
# of Employees | 175 |
Plant Area |
137,600
ft2
|
Annual Production | 1,600
pieces
|
Production Hrs. Annual | 4,278
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $411,308 | 4,244,856 |
kWh
|
$0.097 |
Electricity Demand | $151,740 | 11,318 |
kW-mo/yr
|
$13.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,905 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $41,790 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $29,900 | - | - | - | - | $29,900 | |
02 | 2.4239: Eliminate or reduce compressed air usage | $23,715 | $820 |
$2,375
34,770
kWh
|
$890
-
kW-mo/yr
|
$20,450 | - | |
03 | 2.3212: Optimize plant power factor | $7,880 | $27,800 | - |
$7,880
-
kW-mo/yr
|
- | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $4,870 | $1,500 |
$4,130
60,500
kWh
|
$740
-
kW-mo/yr
|
- | - | |
05 | 2.7124: Make a practice of turning off lights when not needed | $3,920 | - |
$2,570
37,600
kWh
|
$1,350
-
kW-mo/yr
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,290 | - |
$1,830
26,800
kWh
|
$460
-
kW-mo/yr
|
- | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $3,610 | $1,315 |
$2,760
40,400
kWh
|
$850
-
kW-mo/yr
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,910 | $2,130 |
$1,410
30,100
kWh
|
$500
-
kW-mo/yr
|
- | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $480 | - |
$480
7,000
kWh
|
- | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $330 | $160 |
$70
980
kWh
|
$5
-
kW-mo/yr
|
$255 | - | |
TOTAL RECOMMENDED | $78,905 | $33,725 |
$15,625
238,150
kWh
|
$12,675
-
kW-mo/yr
|
$20,705 | $29,900 | ||
TOTAL IMPLEMENTED | $41,790 | $1,660 |
$9,080
132,880
kWh
|
$2,555
-
kW-mo/yr
|
$255 | $29,900 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs