Assessment Year | 2025 |
---|---|
Principal Product | Pharmaceutical Skin care product |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
54,000
ft2
|
Annual Production | 25,000,000
units
|
Production Hrs. Annual | 2,100
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $121,003 | 1,231,494 |
kWh
|
$0.098 |
Electricity Demand | $73,602 | 4,580 |
kW-mo/yr
|
$16.07 |
Electricity Fees | $11,304 | - |
|
- |
Natural Gas | $94,835 | 10,334 |
MMBtu
|
$9.18 |
TOTAL YEARLY COSTS | $300,743 | |||
RECOMMENDED SAVINGS* | $101,477 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $8,633 | - | - | - | - | $8,633 | - | - | |
02 | 2.7261: Install timers and/or thermostats | $1,037 | $3,620 |
$124
1,264
kWh
|
- |
$913
-
MMBtu
|
- | - | - | |
03 | 2.2511: Insulate bare equipment | $4,682 | $2,038 | - | - |
$4,682
-
MMBtu
|
- | - | - | |
04 | 2.9114: Use solar heat to make electricty | $33,422 | $218,140 |
$38,097
387,555
kWh
|
- | - | - | $(-4,675.0) | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,506 | $23,172 |
$8,131
82,720
kWh
|
$7,976
-
kW-mo/yr
|
- | - | $33 | $366 | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,924 | $2,400 |
$1,121
11,401
kWh
|
$803
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,534 | $1,600 |
$8,014
81,530
kWh
|
$2,520
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $2,832 | $75 |
$2,832
28,807
kWh
|
- | - | - | - | - | |
09 | 2.7135: Install occupancy sensors | $71 | $544 |
$49
500
kWh
|
- | - | - | $20 | $1 | |
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $16,968 | $3,500 |
$16,658
169,457
kWh
|
$311
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.7221: Lower temperature during the winter season and vice-versa | $4,869 | - |
$594
6,045
kWh
|
- |
$4,275
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $101,477 | $255,089 |
$75,620
769,279
kWh
|
$11,609
-
kW-mo/yr
|
$9,870
-
MMBtu
|
$8,633 | $(-4,622.1) | $367 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs