Assessment Year | 2023 |
---|---|
Principal Product | Metal staples |
NAICS | 332618: Other Fabricated Wire Product Manufacturing |
SIC | 3496: Miscellaneous Fabricated Wire Products |
Sales Range | $5 M to 10M |
# of Employees | 60 |
Plant Area |
60,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $90,756 | 611,220 |
kWh
|
$0.15 |
Electricity Demand | $52,672 | 2,151 |
kW-mo/yr
|
$24.48 |
Electricity Fees | $3,063 | - |
|
- |
Natural Gas | $20,668 | 1,113 |
MMBtu
|
$18.57 |
TOTAL YEARLY COSTS | $167,158 | |||
RECOMMENDED SAVINGS* | $75,691 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $33,447 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $4,838 | - | - | - | $4,838 | - | - | |
02 | 2.8114: Change rate schedules or other changes in utility service | $6,116 | - | - | - | $6,116 | - | - | |
03 | 2.8123: Pay utility bills on time | $146 | - | - | - | $146 | - | - | |
04 | 2.9114: Use solar heat to make electricty | $39,506 | $192,621 |
$43,302
291,594
kWh
|
- | - | - | $(-3,796.0) | |
05 | 2.7232: Replace existing hvac unit with high efficiency model | $6,045 | $40,103 |
$(-1,888.4)
(-12,717)
kWh
|
$(-426.4)
-
kW-mo/yr
|
- |
$8,360
-
MMBtu
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,547 | $1,283 |
$1,262
8,499
kWh
|
$285
-
kW-mo/yr
|
- | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,607 | $1,900 |
$2,942
19,814
kWh
|
$664
-
kW-mo/yr
|
- | - | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,756 | $225 |
$3,064
20,635
kWh
|
$692
-
kW-mo/yr
|
- | - | - | |
09 | 2.2437: Recover waste heat from equipment | $1,865 | $5,326 |
$561
3,775
kWh
|
$127
-
kW-mo/yr
|
- |
$1,178
-
MMBtu
|
- | |
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,459 | $150 |
$1,191
8,017
kWh
|
$269
-
kW-mo/yr
|
- | - | - | |
11 | 2.6231: Utilize controls to operate equipment only when needed | $4,068 | $75 |
$3,318
22,345
kWh
|
$749
-
kW-mo/yr
|
- | - | - | |
12 | 2.4239: Eliminate or reduce compressed air usage | $791 | $1,804 |
$645
4,343
kWh
|
$146
-
kW-mo/yr
|
- | - | - | |
13 | 2.7261: Install timers and/or thermostats | $1,947 | $1,980 |
$180
1,209
kWh
|
- | - |
$1,768
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $75,691 | $245,466 |
$54,576
367,515
kWh
|
$2,505
-
kW-mo/yr
|
$11,100 |
$11,305
-
MMBtu
|
$(-3,796.0) | ||
TOTAL IMPLEMENTED | $33,447 | $49,061 |
$10,450
70,369
kWh
|
$2,360
-
kW-mo/yr
|
$11,100 |
$9,537
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs