Assessment Year | 2012 |
---|---|
Principal Product | Blended Oils and Tomato Based Products |
NAICS | 311991: Perishable Prepared Food Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 166 |
Plant Area |
200,000
ft2
|
Annual Production | 75,700,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $640,429 | 6,673,117 |
kWh
|
$0.096 |
Electricity Demand | $53,178 | 25,441 |
kW-mo/yr
|
$2.09 |
Natural Gas | $299,065 | 47,592 |
MMBtu
|
$6.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $97,871 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $9,034 | - |
$9,034
95,300
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $742 | - |
$742
7,827
kWh
|
- | |
03 | 2.7122: Disconnect ballasts | $872 | - |
$872
9,198
kWh
|
- | |
04 | 2.2522: Isolate hot or cold equipment | $3,658 | $150 |
$3,658
38,500
kWh
|
- | |
05 | 2.2135: Repair and eliminate steam leaks | $12,041 | $2,000 | - |
$12,041
-
MMBtu
|
|
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,111 | $150 |
$2,111
21,453
kWh
|
- | |
07 | 2.7135: Install occupancy sensors | $9,871 | $2,250 |
$9,871
104,124
kWh
|
- | |
08 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $42,760 | $8,000 |
$42,760
451,072
kWh
|
- | |
09 | 2.4224: Upgrade controls on compressors | $2,473 | $1,600 |
$2,473
26,086
kWh
|
- | |
10 | 2.4157: Establish a predictive maintenance program | $10,016 | $11,318 |
$10,016
105,652
kWh
|
- | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $254 | $300 |
$254
2,680
kWh
|
- | |
12 | 2.7241: Install outside air damper / economizer on hvac unit | $3,869 | $4,800 |
$3,869
40,812
kWh
|
- | |
13 | 2.7425: Clean or color roof to reduce solar load | $170 | $411 |
$170
1,797
kWh
|
- | |
TOTAL RECOMMENDED | $97,871 | $30,979 |
$85,830
904,501
kWh
|
$12,041
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs