Assessment Year | 1991 |
---|---|
Principal Product | ELEC. ROTATING COMPONENT |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 370 |
Plant Area |
n/a
|
Annual Production | 13,500
pieces
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $413,263 | 7,372,509 |
kWh
|
$0.056 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $86,742 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $27,754 | $8,700 |
$27,754
495,604
kWh
|
- | |
02 | 2.2511: Insulate bare equipment | $23,175 | $2,472 |
$23,175
413,834
kWh
|
- | |
03 | 2.7262: Separate controls of air handlers from ac/ heating systems | $13,212 | $7,325 |
$13,212
235,932
kWh
|
- | |
04 | 2.7221: Lower temperature during the winter season and vice-versa | $8,321 | - |
$8,321
148,593
kWh
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,938 | $2,450 |
$2,938
52,462
kWh
|
- | |
06 | 2.6232: Install set-back timers | $1,526 | - |
$1,526
27,257
kWh
|
- | |
07 | 2.7227: Use water on air conditioning exchanger to improve heat transfer and increase air conditioner efficiency | $1,477 | - |
$1,477
26,377
kWh
|
- | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,412 | $620 |
$1,412
25,205
kWh
|
- | |
09 | 2.7111: Reduce illumination to minimum necessary levels | $1,462 | - |
$1,379
24,619
kWh
|
$83 | |
10 | 2.7212: Install or upgrade insulation on hvac distribution systems | $1,165 | $799 |
$1,165
20,809
kWh
|
- | |
11 | 2.4221: Install compressor air intakes in coolest locations | $1,034 | $3,340 |
$1,034
18,464
kWh
|
- | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,839 | $3,550 |
$2,839
50,703
kWh
|
- | |
13 | 2.7229: Air condition only space necessary | $427 | $675 |
$427
7,620
kWh
|
- | |
TOTAL RECOMMENDED | $86,742 | $29,931 |
$86,659
1,547,479
kWh
|
$83 | ||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs