Assessment Year | 1985 |
---|---|
Principal Product | FERRITE CORES & DEVICES |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 61 |
Plant Area |
n/a
|
Annual Production | 200,000
lb
|
Production Hrs. Annual | 4,600
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $139,575 | 1,423,798 |
kWh
|
$0.098 |
Natural Gas | $17,542 | 2,694 |
MMBtu
|
$6.51 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,995 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,768 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,145 | $292 |
$3,145
32,239
kWh
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $112 | $100 |
$112
1,172
kWh
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $583 | - |
$583
5,862
kWh
|
- | - | |
04 | 2.6121: Reduce hot water temperature to the minimum required | $423 | - |
$423
4,396
kWh
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $431 | $234 |
$431
4,396
kWh
|
- | - | |
06 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $649 | $1,570 |
$899
9,086
kWh
|
$(-250.0)
-
MMBtu
|
- | |
07 | 2.4312: Improve lubrication practices | $1,193 | - |
$1,313
13,482
kWh
|
- | $(-120.0) | |
08 | 2.2511: Insulate bare equipment | $18,809 | $4,989 |
$18,809
191,970
kWh
|
- | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $357 | $33 | - |
$357
-
MMBtu
|
- | |
10 | 2.7261: Install timers and/or thermostats | $4,293 | $420 | - |
$4,293
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $29,995 | $7,638 |
$25,715
262,603
kWh
|
$4,400
-
MMBtu
|
$(-120.0) | ||
TOTAL IMPLEMENTED | $5,768 | $553 |
$1,118
11,430
kWh
|
$4,650
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs