Assessment Year | 2021 |
---|---|
Principal Product | Liquid and Solid Chocolate |
NAICS | 311351: Chocolate and Confectionery Manufacturing from Cacao Beans |
SIC | 2066: Chocolate and Cocoa Products |
Sales Range | $100 M to 500M |
# of Employees | 75 |
Plant Area |
200,000
ft2
|
Annual Production | 88,000
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $931,710 | 7,602,066 |
kWh
|
$0.12 | |
Electricity Demand | $714,150 | 20,208 |
kW-mo/yr
|
$35.34 | |
Electricity Fees | $23,679 | - |
|
- | |
Natural Gas | $88,446 | 7,963 |
MMBtu
|
$11.11 | |
Waste Disposal Costs | |||||
Water Usage | $24,416 | 2,726 |
Tgal
|
$8.96 | |
Water Disposal | $18,022 | 2,726 |
Tgal
|
$6.61 | |
TOTAL YEARLY COSTS | $1,800,423 | ||||
RECOMMENDED SAVINGS* | $617,742 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $43,600 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Primary Raw Material Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $16,373 | $200 |
$11,738
95,740
kWh
|
$4,635
-
kW-mo/yr
|
- | - | - | - | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,781 | $1,200 |
$18,781
162,976
kWh
|
- | - | - | - | - | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $332 | $67 |
$238
1,941
kWh
|
$94
-
kW-mo/yr
|
- | - | - | - | - | - | |
04 | 2.2628: Utilize a less expensive cooling method | $33,236 | $25,695 |
$33,236
271,092
kWh
|
- | - | - | - | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $46,961 | $45,208 |
$25,728
209,853
kWh
|
$19,614
-
kW-mo/yr
|
- | - | - | $2,034 | $(-415.0) | - | |
06 | 2.3132: Recharge batteries on during off-peak demand periods | $1,350 | $4,996 | - | - | $1,350 | - | - | - | - | - | |
07 | 2.1224: Replace boiler | $14,321 | $72,000 | - | - | - |
$14,321
-
MMBtu
|
- | - | - | - | |
08 | 2.9114: Use solar heat to make electricty | $343,451 | $2,394,442 |
$343,451
2,801,396
kWh
|
- | - | - | - | - | - | - | |
09 | 2.4222: Install adequate dryers on air lines to eliminate blowdown | $134,491 | $56,667 |
$14,491
(-118,203)
kWh
|
- | - | - | - | - | - | $120,000 | |
10 | 2.8117: Install sub-metering equipment | $8,446 | $6,896 | - | - | - | - |
$8,446
-
Tgal
|
- | - | - | |
TOTAL RECOMMENDED | $617,742 | $2,607,371 |
$447,663
3,424,795
kWh
|
$24,343
-
kW-mo/yr
|
$1,350 |
$14,321
-
MMBtu
|
$8,446
-
Tgal
|
$2,034 | $(-415.0) | $120,000 | ||
TOTAL IMPLEMENTED | $43,600 | $8,296 |
$30,519
258,716
kWh
|
$4,635
-
kW-mo/yr
|
- | - |
$8,446
-
Tgal
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Primary Raw Material Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs