Assessment Year | 2011 |
---|---|
Principal Product | PVC, HDPE, ABS Pipe |
NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing |
SIC | 3084: Plastics Pipe |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
252,799
ft2
|
Annual Production | 90,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,650,036 | 21,175,483 |
kWh
|
$0.078 |
Electricity Demand | $482,994 | 50,328 |
kW-mo/yr
|
$9.60 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $163,652 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $54,244 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $6,724 | - |
$6,724
89,177
kWh
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,312 | - |
$4,312
57,182
kWh
|
- | - | |
03 | 2.6231: Utilize controls to operate equipment only when needed | $3,795 | $4,576 |
$3,795
50,333
kWh
|
- | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,313 | $7,243 |
$8,110
107,570
kWh
|
$3,203
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,833 | $5,753 |
$3,465
45,961
kWh
|
$1,368
-
kW-mo/yr
|
- | |
06 | 2.4227: Use compressor air filters | $1,038 | $1,467 |
$1,038
13,763
kWh
|
- | - | |
07 | 2.4133: Use most efficient type of electric motors | $13,112 | $6,182 |
$9,087
120,518
kWh
|
$4,025
-
kW-mo/yr
|
- | |
08 | 2.7135: Install occupancy sensors | $3,218 | $6,195 |
$2,316
30,719
kWh
|
$902
-
kW-mo/yr
|
- | |
09 | 2.2511: Insulate bare equipment | $8,140 | $22,037 |
$8,140
107,961
kWh
|
- | - | |
10 | 2.2622: Replace existing chiller with high efficiency model | $4,772 | $18,000 |
$3,420
45,360
kWh
|
$1,352
-
kW-mo/yr
|
- | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,959 | $41,361 |
$5,631
74,677
kWh
|
- | $328 | |
12 | 2.9114: Use solar heat to make electricty | $96,436 | $3,735,000 |
$68,850
866,812
kWh
|
$27,586
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $163,652 | $3,847,814 |
$124,888
1,610,033
kWh
|
$38,436
-
kW-mo/yr
|
$328 | ||
TOTAL IMPLEMENTED | $54,244 | $60,682 |
$44,296
587,492
kWh
|
$9,948
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs