Assessment Year | 2012 |
---|---|
Principal Product | Rubber Goods |
NAICS | 326291: Rubber Product Manufacturing for Mechanical Use |
SIC | 3061: Molded, Extruded, and Lathe-Cut Mechanical Rubber Goods |
Sales Range | $50 M to 100M |
# of Employees | 470 |
Plant Area |
326,000
ft2
|
Annual Production | 3,820
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Arkansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,687,271 | 27,163,800 |
kWh
|
$0.062 |
Electricity Demand | $519,429 | 54,391 |
kW-mo/yr
|
$9.55 |
Natural Gas | $1,058,984 | 199,504 |
MMBtu
|
$5.31 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $365,841 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,138 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1224: Replace boiler | $228,516 | $1,085,000 | - | - |
$228,516
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,541 | $68,775 |
$7,541
121,632
kWh
|
- | - | |
03 | 2.7135: Install occupancy sensors | $194 | $3,150 |
$194
3,128
kWh
|
- | - | |
04 | 2.4322: Use or replace with energy efficient substitutes | $19,699 | $65,000 |
$19,699
317,725
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,478 | $1,500 |
$12,478
201,262
kWh
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,119 | $538 |
$1,119
18,044
kWh
|
- | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,300 | $450 |
$2,300
37,102
kWh
|
- | - | |
08 | 2.2691: Shut off cooling if cold outside air will cool process | $62,755 | $31,500 |
$62,755
1,012,176
kWh
|
- | - | |
09 | 2.7262: Separate controls of air handlers from ac/ heating systems | $15,683 | $15,683 |
$15,683
252,945
kWh
|
- | - | |
10 | 2.6232: Install set-back timers | $929 | $937 | - | - |
$929
-
MMBtu
|
|
11 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $8,292 | $406,800 |
$327
5,248
kWh
|
- |
$7,965
-
MMBtu
|
|
12 | 2.3132: Recharge batteries on during off-peak demand periods | $6,335 | - | - |
$6,335
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $365,841 | $1,679,333 |
$122,096
1,969,262
kWh
|
$6,335
-
kW-mo/yr
|
$237,410
-
MMBtu
|
||
TOTAL IMPLEMENTED | $21,138 | $70,813 |
$21,138
340,938
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs