Assessment Year | 1991 |
---|---|
Principal Product | VINYL FLOOR COVERING |
NAICS |
n/a
|
SIC | 3996: Linoleum, Asphalted-Felt-Base, and Other Hard Surface Floor Coverings, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 154
thousand feet
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $579,310 | 13,649,180 |
kWh
|
$0.042 |
Natural Gas | $328,854 | 151,090 |
MMBtu
|
$2.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $69,730 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $69,730 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $355 | $245 |
$145
4,103
kWh
|
$210
-
MMBtu
|
|
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,004 | $6,200 |
$4,004
77,374
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,241 | $791 |
$1,241
25,205
kWh
|
- | |
04 | 2.7141: Lower light fixtures in high ceiling areas | $14,080 | $38,500 |
$14,080
394,490
kWh
|
- | |
05 | 2.7261: Install timers and/or thermostats | $1,481 | $1,800 | - |
$1,481
-
MMBtu
|
|
06 | 2.6232: Install set-back timers | $19,001 | $13,510 |
$19,001
535,170
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $846 | $1,336 |
$846
12,896
kWh
|
- | |
08 | 2.2135: Repair and eliminate steam leaks | $443 | $740 | - |
$443
-
MMBtu
|
|
09 | 2.4221: Install compressor air intakes in coolest locations | $2,226 | $2,900 |
$444
12,309
kWh
|
$1,782
-
MMBtu
|
|
10 | 2.2414: Use waste heat from hot flue gases to preheat | $26,053 | $16,500 |
$(-1,079.0)
(-19,343)
kWh
|
$27,132
-
MMBtu
|
|
TOTAL RECOMMENDED | $69,730 | $82,522 |
$38,682
1,042,204
kWh
|
$31,048
-
MMBtu
|
||
TOTAL IMPLEMENTED | $69,730 | $82,522 |
$38,682
1,042,204
kWh
|
$31,048
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs