Assessment Year | 2025 |
---|---|
Principal Product | Metal Sheets and Panels |
NAICS | 336411: Aircraft Manufacturing |
SIC | 3721: Aircraft |
Sales Range | $50 M to 100M |
# of Employees | 240 |
Plant Area |
261,000
ft2
|
Annual Production | 344,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $157,288 | 2,754,001 |
kWh
|
$0.057 |
Electricity Demand | $80,092 | 5,530 |
kW-mo/yr
|
$14.48 |
Electricity Fees | $60,177 | - |
|
- |
TOTAL YEARLY COSTS | $297,557 | |||
RECOMMENDED SAVINGS* | $25,420 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $2,522 | - |
$1,697
29,773
kWh
|
$825
-
kW-mo/yr
|
|
02 | 2.6231: Utilize controls to operate equipment only when needed | $3,243 | - |
$2,179
38,220
kWh
|
$1,064
-
kW-mo/yr
|
|
03 | 2.7444: Close holes and openings in building such as broken windows | $5,173 | $485 |
$3,479
61,030
kWh
|
$1,694
-
kW-mo/yr
|
|
04 | 2.7229: Air condition only space necessary | $5,341 | $960 |
$3,589
62,971
kWh
|
$1,752
-
kW-mo/yr
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,193 | $1,665 |
$4,832
84,770
kWh
|
$2,361
-
kW-mo/yr
|
|
06 | 2.6218: Turn off equipment when not in use | $1,948 | $2,600 |
$1,948
34,173
kWh
|
- | |
TOTAL RECOMMENDED | $25,420 | $5,710 |
$17,724
310,937
kWh
|
$7,696
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs