Assessment Year | 2003 |
---|---|
Principal Product | Plastic containers |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 125 |
Plant Area |
105,000
ft2
|
Annual Production | 8,400,000
pieces
|
Production Hrs. Annual | 8,520
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $3,091,759 | 43,448,154 |
kWh
|
$0.071 |
Electricity Demand | $710,839 | 74,417 |
kW-mo/yr
|
$9.55 |
Electricity Fees | $3,833 | - |
|
- |
Natural Gas | $53,433 | 6,333 |
MMBtu
|
$8.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $2,138,058 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,968 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $1,726,195 | $11,884,320 |
$3,096,462
43,448,154
kWh
|
$710,839
-
kW-mo/yr
|
$(-2,194,856.0)
-
MMBtu
|
- | $113,750 | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $50,349 | $28,595 |
$50,349
800,065
kWh
|
- | - | - | - | |
03 | 2.2612: Use cooling tower water instead of refrigeration | $32,261 | $17,920 |
$32,261
470,966
kWh
|
- | - | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $12,447 | $7,000 |
$12,447
181,700
kWh
|
- | - | - | - | |
05 | 2.2628: Utilize a less expensive cooling method | $10,042 | $6,200 |
$10,042
146,600
kWh
|
- | - | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $295,995 | $436,450 |
$259,385
3,787,000
kWh
|
$36,610
-
kW-mo/yr
|
- | - | - | |
07 | 2.7261: Install timers and/or thermostats | $5,220 | $650 |
$1,322
19,700
kWh
|
- |
$3,898
-
MMBtu
|
- | - | |
08 | 2.4151: Develop a repair/replace policy | $3,581 | $5,497 |
$2,841
41,473
kWh
|
$740
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,968 | $15,662 |
$234
3,400
kWh
|
$37
-
kW-mo/yr
|
- | $1,697 | - | |
TOTAL RECOMMENDED | $2,138,058 | $12,402,294 |
$3,465,343
48,899,058
kWh
|
$748,226
-
kW-mo/yr
|
$(-2,190,958.0)
-
MMBtu
|
$1,697 | $113,750 | ||
TOTAL IMPLEMENTED | $1,968 | $15,662 |
$234
3,400
kWh
|
$37
-
kW-mo/yr
|
- | $1,697 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs