| Assessment Year | 1984 |
|---|---|
| Principal Product | NEWSPAPERS, CIRCULARS |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $10 M to 50M |
| # of Employees | 200 |
| Plant Area |
n/a
|
| Annual Production | 4,800
ton
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $81,716 | 1,699,883 |
kWh
|
$0.048 |
| Natural Gas | $6,968 | 1,376 |
MMBtu
|
$5.06 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,133 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $14,133 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,798 | $2,178 |
$4,798
99,648
kWh
|
- | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $166 | $300 | - |
$166
-
MMBtu
|
|
| 03 | 2.2437: Recover waste heat from equipment | $428 | $100 | - |
$428
-
MMBtu
|
|
| 04 | 2.7444: Close holes and openings in building such as broken windows | $528 | $21 |
$85
1,758
kWh
|
$443
-
MMBtu
|
|
| 05 | 2.7492: Use proper thickness of insulation on building envelope | $145 | $221 | - |
$145
-
MMBtu
|
|
| 06 | 2.4221: Install compressor air intakes in coolest locations | $288 | $275 |
$288
5,862
kWh
|
- | |
| 07 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,282 | - |
$4,282
-
kWh
|
- | |
| 08 | 2.7261: Install timers and/or thermostats | $2,099 | $721 |
$1,516
31,653
kWh
|
$583
-
MMBtu
|
|
| 09 | 2.7262: Separate controls of air handlers from ac/ heating systems | $370 | $400 |
$370
7,620
kWh
|
- | |
| 10 | 3.4156: Use flow control valves on equipment to optimize water use | $1,029 | $25 | - |
$1,029
-
MMBtu
|
|
| TOTAL RECOMMENDED | $14,133 | $4,241 |
$11,339
146,541
kWh
|
$2,794
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $14,133 | $4,241 |
$11,339
146,541
kWh
|
$2,794
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs