| Assessment Year | 2026 |
|---|---|
| Principal Product | Furniture and Fixtures |
| NAICS | 321219: Reconstituted Wood Product Manufacturing |
| SIC | 2599: Furniture and Fixtures, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 140 |
| Plant Area |
92,000
ft2
|
| Annual Production | 1,500
thousand feet
|
| Production Hrs. Annual | 2,413
hrs
|
| Location (State) | Arizona |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $50,138 | 469,720 |
kWh
|
$0.11 | |
| Electricity Demand | $8,637 | 1,729 |
kW-mo/yr
|
$5.00 | |
| Electricity Fees | $4,928 | - |
|
- | |
| LPG | $3,193 | 46 |
MMBtu
|
$69.26 | |
| Fuel Oil #2 | $49,733 | 1,935 |
MMBtu
|
$25.70 | |
| Waste Disposal Costs | |||||
| Water Usage | $7,591 | 1,663 |
Tgal
|
$4.56 | |
| Solid Waste (non-haz) | $138,225 | 2,400,000 |
lb
|
$0.058 | |
| TOTAL YEARLY COSTS | $262,445 | ||||
| RECOMMENDED SAVINGS* | $100,626 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4321: Upgrade obsolete equipment | $81,446 | $350,000 |
$1,184
11,100
kWh
|
$262
-
kW-mo/yr
|
- | $80,000 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,397 | $7,852 |
$4,403
41,264
kWh
|
$764
-
kW-mo/yr
|
- | $230 | |
| 03 | 2.6231: Utilize controls to operate equipment only when needed | $3,915 | $2,204 |
$1,570
14,716
kWh
|
$545
-
kW-mo/yr
|
- | $1,800 | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,939 | $11,910 |
$2,406
22,548
kWh
|
$533
-
kW-mo/yr
|
- | - | |
| 05 | 2.6218: Turn off equipment when not in use | $1,828 | $62 |
$1,590
14,898
kWh
|
$438
-
kW-mo/yr
|
$(-200.0) | - | |
| 06 | 2.7261: Install timers and/or thermostats | $1,823 | $1,826 |
$1,466
13,739
kWh
|
$357
-
kW-mo/yr
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,673 | $516 |
$1,370
12,837
kWh
|
$303
-
kW-mo/yr
|
- | - | |
| 08 | 2.6211: Conserve energy by efficient use of vending machines | $1,381 | $547 |
$1,297
12,154
kWh
|
$84
-
kW-mo/yr
|
- | - | |
| 09 | 2.4221: Install compressor air intakes in coolest locations | $224 | $1,573 |
$183
1,715
kWh
|
$41
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $100,626 | $376,490 |
$15,469
144,971
kWh
|
$3,327
-
kW-mo/yr
|
$(-200.0) | $82,030 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs