Assessment Year | 2025 |
---|---|
Principal Product | PCBA’s & Electro-Mechanical Assemblies |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
70,000
ft2
|
Annual Production | 130,000
pieces
|
Production Hrs. Annual | 5,460
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $117,083 | 1,581,876 |
kWh
|
$0.074 |
Electricity Demand | $21,933 | 4,395 |
kW-mo/yr
|
$4.99 |
Natural Gas | $12,218 | 1,772 |
MMBtu
|
$6.90 |
TOTAL YEARLY COSTS | $151,234 | |||
RECOMMENDED SAVINGS* | $13,640 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,920 | $1,550 |
$4,286
57,907
kWh
|
$634
-
kW-mo/yr
|
- | |
02 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $2,427 | $11,850 |
$(-682.0)
(-9,211)
kWh
|
$(-100.0)
-
kW-mo/yr
|
$3,209
-
MMBtu
|
|
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,393 | $9,261 |
$181
2,455
kWh
|
$25
-
kW-mo/yr
|
$2,187
-
MMBtu
|
|
04 | 2.6232: Install set-back timers | $1,875 | $1,135 |
$1,254
16,949
kWh
|
$110
-
kW-mo/yr
|
$511
-
MMBtu
|
|
05 | 2.2511: Insulate bare equipment | $964 | $412 |
$849
10,624
kWh
|
$115
-
kW-mo/yr
|
- | |
06 | 2.4239: Eliminate or reduce compressed air usage | $814 | $894 |
$709
9,585
kWh
|
$105
-
kW-mo/yr
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $247 | $108 |
$217
2,938
kWh
|
$30
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $13,640 | $25,210 |
$6,814
91,247
kWh
|
$919
-
kW-mo/yr
|
$5,907
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs