| Assessment Year | 2025 |
|---|---|
| Principal Product | Automotive Oil |
| NAICS | 324191: Petroleum Lubricating Oil and Grease Manufacturing |
| SIC | 2992: Lubricating Oils and Greases |
| Sales Range | $100 M to 500M |
| # of Employees | 160 |
| Plant Area |
244,600
ft2
|
| Annual Production | 22,220
Tgal
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | West Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $510,287 | 12,723,945 |
kWh
|
$0.040 |
| Electricity Demand | $248,994 | 16,870 |
kW-mo/yr
|
$14.76 |
| Electricity Fees | $48,634 | - |
|
- |
| Natural Gas | $127,074 | 30,163 |
MMBtu
|
$4.21 |
| TOTAL YEARLY COSTS | $934,989 | |||
| RECOMMENDED SAVINGS* | $66,623 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $43,878 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,491 | $60,024 |
$12,819
319,613
kWh
|
$6,672
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.7135: Install occupancy sensors | $15,762 | $7,782 |
$10,360
258,355
kWh
|
$5,402
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4224: Upgrade controls on compressors | $10,271 | $5,515 |
$6,758
168,536
kWh
|
$3,513
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.4157: Establish a predictive maintenance program | $7,107 | $5,200 |
$9,548
238,099
kWh
|
$4,827
-
kW-mo/yr
|
- | $(-7,268.0) | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,687 | $1,418 |
$4,443
110,790
kWh
|
$2,244
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.2425: Use flue gases to heat process or service water | $3,254 | $14,320 | - | - |
$3,254
-
MMBtu
|
- | - | |
| 07 | 2.4151: Develop a repair/replace policy | $2,517 | $12,170 |
$1,948
48,584
kWh
|
$989
-
kW-mo/yr
|
- | - | $(-420.0) | |
| 08 | 2.4239: Eliminate or reduce compressed air usage | $1,244 | $540 |
$831
20,717
kWh
|
$413
-
kW-mo/yr
|
- | - | - | |
| 09 | 2.2511: Insulate bare equipment | $290 | $446 | - | - |
$290
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $66,623 | $107,415 |
$46,707
1,164,694
kWh
|
$24,060
-
kW-mo/yr
|
$3,544
-
MMBtu
|
$(-7,268.0) | $(-420.0) | ||
| TOTAL IMPLEMENTED | $43,878 | $33,071 |
$33,888
845,081
kWh
|
$17,388
-
kW-mo/yr
|
$290
-
MMBtu
|
$(-7,268.0) | $(-420.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs