Assessment Year | 2024 |
---|---|
Principal Product | Injection/Compression molded plastic |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3466: Crowns and Closures |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
128,000
ft2
|
Annual Production | 2,900,000,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,037,931 | 14,449,664 |
kWh
|
$0.072 |
Electricity Demand | $104,699 | 24,513 |
kW-mo/yr
|
$4.27 |
Natural Gas | $6,163 | 1,860 |
MMBtu
|
$3.31 |
TOTAL YEARLY COSTS | $1,148,793 | |||
RECOMMENDED SAVINGS* | $88,350 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,904 | $15,193 |
$17,478
243,420
kWh
|
$1,426
-
kW-mo/yr
|
- | - | - | |
02 | 2.4224: Upgrade controls on compressors | $16,714 | $10,679 |
$15,809
187,533
kWh
|
$905
-
kW-mo/yr
|
- | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $16,594 | $38,917 |
$14,574
202,987
kWh
|
$2,020
-
kW-mo/yr
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $8,306 | $17,145 |
$7,678
106,941
kWh
|
$628
-
kW-mo/yr
|
- | - | - | |
05 | 2.4157: Establish a predictive maintenance program | $7,906 | $5,200 |
$12,541
174,661
kWh
|
$1,025
-
kW-mo/yr
|
- | $(-5,660.0) | - | |
06 | 2.2625: Chill water to the highest temperature possible | $4,058 | $5,330 |
$3,751
52,244
kWh
|
$307
-
kW-mo/yr
|
- | - | - | |
07 | 2.7135: Install occupancy sensors | $3,901 | $6,364 |
$3,596
50,084
kWh
|
$305
-
kW-mo/yr
|
- | - | - | |
08 | 2.6242: Minimize operation of equipment maintained in standby condition | $3,623 | $1,200 |
$3,350
46,656
kWh
|
$273
-
kW-mo/yr
|
- | - | - | |
09 | 2.4151: Develop a repair/replace policy | $3,020 | $1,180 |
$2,822
39,299
kWh
|
$231
-
kW-mo/yr
|
- | - | $(-33.0) | |
10 | 2.4221: Install compressor air intakes in coolest locations | $1,918 | $2,094 |
$1,721
23,964
kWh
|
$141
-
kW-mo/yr
|
$56
-
MMBtu
|
- | - | |
11 | 2.7241: Install outside air damper / economizer on hvac unit | $1,525 | $7,504 |
$1,260
14,943
kWh
|
$265
-
kW-mo/yr
|
- | - | - | |
12 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $799 | $1,648 |
$739
10,289
kWh
|
$60
-
kW-mo/yr
|
- | - | - | |
13 | 2.4231: Reduce the pressure of compressed air to the minimum required | $768 | $176 |
$708
9,861
kWh
|
$60
-
kW-mo/yr
|
- | - | - | |
14 | 2.1221: Replace obsolete burners with more efficient ones | $314 | $1,322 | - | - |
$314
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $88,350 | $113,952 |
$86,027
1,162,882
kWh
|
$7,646
-
kW-mo/yr
|
$370
-
MMBtu
|
$(-5,660.0) | $(-33.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |