| Assessment Year | 2024 |
|---|---|
| Principal Product | Cabinet doors, frames, door fronts |
| NAICS | 337110: Wood Kitchen Cabinet and Countertop Manufacturing |
| SIC | 2434: Wood Kitchen Cabinets |
| Sales Range | $50 M to 100M |
| # of Employees | 250 |
| Plant Area |
240,000
ft2
|
| Annual Production | 1,800,000
units
|
| Production Hrs. Annual | 3,840
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,149,572 | 13,955,120 |
kWh
|
$0.082 |
| Natural Gas | $239,985 | 35,137 |
MMBtu
|
$6.83 |
| TOTAL YEARLY COSTS | $1,389,557 | |||
| RECOMMENDED SAVINGS* | $202,078 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,918 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $100,715 | $390,000 |
$100,715
1,222,272
kWh
|
- | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $61,926 | $238,677 |
$61,926
751,524
kWh
|
- | - | |
| 03 | 2.4224: Upgrade controls on compressors | $7,375 | $13,475 |
$7,375
89,497
kWh
|
- | - | |
| 04 | 2.2425: Use flue gases to heat process or service water | $7,315 | $22,800 | - |
$7,315
-
MMBtu
|
- | |
| 05 | 2.4157: Establish a predictive maintenance program | $6,272 | $1,500 |
$7,189
87,245
kWh
|
- | $(-917.0) | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,064 | $3,296 |
$5,064
61,451
kWh
|
- | - | |
| 07 | 2.2511: Insulate bare equipment | $3,763 | $2,971 | - |
$3,763
-
MMBtu
|
- | |
| 08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,306 | $1,070 | - |
$2,306
-
MMBtu
|
- | |
| 09 | 2.4151: Develop a repair/replace policy | $2,096 | $1,417 |
$2,696
32,717
kWh
|
- | $(-600.0) | |
| 10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,835 | $150 |
$1,835
22,273
kWh
|
- | - | |
| 11 | 2.4221: Install compressor air intakes in coolest locations | $1,829 | $9,140 |
$1,344
16,305
kWh
|
$485
-
MMBtu
|
- | |
| 12 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,582 | $375 |
$1,582
19,193
kWh
|
- | - | |
| TOTAL RECOMMENDED | $202,078 | $684,871 |
$189,726
2,302,477
kWh
|
$13,869
-
MMBtu
|
$(-1,517.0) | ||
| TOTAL IMPLEMENTED | $22,918 | $10,779 |
$18,366
222,879
kWh
|
$6,069
-
MMBtu
|
$(-1,517.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs