| Assessment Year | 2024 |
|---|---|
| Principal Product | Building Envelope Installation |
| NAICS | 332322: Sheet Metal Work Manufacturing |
| SIC | 3444: Sheet Metal Work |
| Sales Range | $50 M to 100M |
| # of Employees | 100 |
| Plant Area |
141,416
ft2
|
| Annual Production | 10,000
units
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | West Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $96,742 | 1,272,700 |
kWh
|
$0.076 |
| Electricity Demand | $36,218 | 3,433 |
kW-mo/yr
|
$10.55 |
| Electricity Fees | $1,260 | - |
|
- |
| Natural Gas | $21,189 | 2,234 |
MMBtu
|
$9.48 |
| TOTAL YEARLY COSTS | $155,409 | |||
| RECOMMENDED SAVINGS* | $8,370 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,518 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $3,906 | $461 |
$2,229
29,328
kWh
|
$1,677
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,933 | $4,143 |
$1,170
15,406
kWh
|
$763
-
kW-mo/yr
|
- | |
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,852 | $3,768 |
$(-18.0)
(-232)
kWh
|
- |
$1,870
-
MMBtu
|
|
| 04 | 2.7224: Reduce space conditioning during non-working hours | $332 | $1,525 | - | - |
$332
-
MMBtu
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $220 | $181 |
$125
1,649
kWh
|
$95
-
kW-mo/yr
|
- | |
| 06 | 2.4224: Upgrade controls on compressors | $127 | $635 |
$64
842
kWh
|
$63
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $8,370 | $10,713 |
$3,570
46,993
kWh
|
$2,598
-
kW-mo/yr
|
$2,202
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $6,518 | $6,945 |
$3,588
47,225
kWh
|
$2,598
-
kW-mo/yr
|
$332
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs