| Assessment Year | 2020 |
|---|---|
| Principal Product | processed meat |
| NAICS | 311612: Meat Processed from Carcasses |
| SIC | 2011: Meat Packing Plants |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
78,000
ft2
|
| Annual Production | 25,000
lb
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | West Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $69,522 | 1,986,540 |
kWh
|
$0.035 | |
| Electricity Demand | $79,373 | 4,395 |
kW-mo/yr
|
$18.06 | |
| Electricity Fees | $4,735 | - |
|
- | |
| Natural Gas | $9,977 | 1,292 |
MMBtu
|
$7.72 | |
| Waste Disposal Costs | |||||
| Water Usage | $1,440 | 244 |
Tgal
|
$5.90 | |
| Water Disposal | $1,664 | 244 |
Tgal
|
$6.82 | |
| TOTAL YEARLY COSTS | $166,711 | ||||
| RECOMMENDED SAVINGS* | $77,893 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $10,239 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 4.126: Install sensors to detect defects | $30,600 | $10,470 | - | - | - | - | - | $30,600 | |
| 02 | 2.2622: Replace existing chiller with high efficiency model | $28,134 | $48,344 |
$16,467
470,494
kWh
|
$11,667
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.4145: Install isolation transformer on adjustable frequency drive | $8,920 | $11,220 |
$4,586
131,040
kWh
|
$4,334
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.7135: Install occupancy sensors | $7,292 | $6,768 |
$2,506
71,598
kWh
|
$4,786
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 3.5131: Recycle white water | $1,467 | $3,170 |
$(-23.0)
(-671)
kWh
|
- |
$691
-
Tgal
|
$799
-
Tgal
|
- | - | |
| 06 | 2.4322: Use or replace with energy efficient substitutes | $916 | $1,021 |
$1,696
48,466
kWh
|
$(-780.0)
-
kW-mo/yr
|
- | - | - | - | |
| 07 | 2.4151: Develop a repair/replace policy | $564 | $613 |
$427
12,189
kWh
|
$307
-
kW-mo/yr
|
- | - | $(-170.0) | - | |
| TOTAL RECOMMENDED | $77,893 | $81,606 |
$25,659
733,116
kWh
|
$20,314
-
kW-mo/yr
|
$691
-
Tgal
|
$799
-
Tgal
|
$(-170.0) | $30,600 | ||
| TOTAL IMPLEMENTED | $10,239 | $11,572 |
$4,606
131,582
kWh
|
$4,313
-
kW-mo/yr
|
$691
-
Tgal
|
$799
-
Tgal
|
$(-170.0) | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs