Assessment Year | 2019 |
---|---|
Principal Product | Glass display panels |
NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231: Glass Products, Made of Purchased Glass |
Sales Range | $5 M to 10M |
# of Employees | 50 |
Plant Area |
90,000
ft2
|
Annual Production | 12,000,000
units
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $65,084 | 1,846,290 |
kWh
|
$0.035 |
Electricity Demand | $125,662 | 7,110 |
kW-mo/yr
|
$17.67 |
Electricity Fees | $604 | - |
|
- |
Natural Gas | $70,480 | 9,137 |
MMBtu
|
$7.71 |
TOTAL YEARLY COSTS | $261,830 | |||
RECOMMENDED SAVINGS* | $27,092 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,810 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1212: Operate boilers on high fire setting | $14,618 | $15,000 | - | - |
$14,618
-
MMBtu
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $7,189 | $3,000 | - | - |
$7,209
-
MMBtu
|
$(-20.0) | |
03 | 2.7135: Install occupancy sensors | $1,785 | $3,399 |
$513
14,537
kWh
|
$1,272
-
kW-mo/yr
|
- | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,129 | $1,000 |
$1,129
31,974
kWh
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,078 | $910 |
$318
9,008
kWh
|
$760
-
kW-mo/yr
|
- | - | |
06 | 2.4224: Upgrade controls on compressors | $535 | $3,000 |
$535
15,142
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $523 | $471 |
$223
6,307
kWh
|
$300
-
kW-mo/yr
|
- | - | |
08 | 2.4151: Develop a repair/replace policy | $120 | $533 |
$103
2,911
kWh
|
$177
-
kW-mo/yr
|
- | $(-160.0) | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $115 | - |
$44
1,252
kWh
|
$71
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $27,092 | $27,313 |
$2,865
81,131
kWh
|
$2,580
-
kW-mo/yr
|
$21,827
-
MMBtu
|
$(-180.0) | ||
TOTAL IMPLEMENTED | $10,810 | $8,313 |
$1,201
34,015
kWh
|
$2,580
-
kW-mo/yr
|
$7,209
-
MMBtu
|
$(-180.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs