Assessment Year | 2018 |
---|---|
Principal Product | Food grade plastic containers and covers |
NAICS | 326111: Plastics Bag and Pouch Manufacturing |
SIC | 2673: Plastics, Foil, and Coated Paper Bags |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
180,000
ft2
|
Annual Production | 90,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,395,168 | 28,676,493 |
kWh
|
$0.049 | |
Electricity Demand | $746,121 | 50,505 |
kW-mo/yr
|
$14.77 | |
Electricity Fees | $359 | - |
|
- | |
Natural Gas | $90,160 | 27,262 |
MMBtu
|
$3.31 | |
Waste Disposal Costs | |||||
Water Usage | $6,351 | 765 |
Tgal
|
$8.30 | |
Water Disposal | $5,820 | 765 |
Tgal
|
$7.60 | |
TOTAL YEARLY COSTS | $2,243,979 | ||||
RECOMMENDED SAVINGS* | $167,235 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $34,793 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $122,928 | $148,200 |
$122,928
2,524,199
kWh
|
- | - | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,683 | $2,990 |
$5,683
116,684
kWh
|
- | - | - | - | - | |
03 | 2.4151: Develop a repair/replace policy | $15,386 | $868 |
$11,073
227,371
kWh
|
$4,593
-
kW-mo/yr
|
- | - | - | $(-280.0) | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,976 | $468 |
$7,756
159,257
kWh
|
$3,220
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4224: Upgrade controls on compressors | $7,457 | $30,875 |
$4,665
95,800
kWh
|
$2,792
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,692 | $1,000 | - | - |
$1,867
-
MMBtu
|
- | - | $(-175.0) | |
07 | 2.2511: Insulate bare equipment | $1,056 | $247 | - | - |
$1,056
-
MMBtu
|
- | - | - | |
08 | 3.4151: Minimize water usage | $2,057 | $1,050 | - | - | - |
$1,212
-
Tgal
|
$1,110
-
Tgal
|
$(-265.0) | |
TOTAL RECOMMENDED | $167,235 | $185,698 |
$152,105
3,123,311
kWh
|
$10,605
-
kW-mo/yr
|
$2,923
-
MMBtu
|
$1,212
-
Tgal
|
$1,110
-
Tgal
|
$(-720.0) | ||
TOTAL IMPLEMENTED | $34,793 | $5,573 |
$24,512
503,312
kWh
|
$7,813
-
kW-mo/yr
|
$2,923
-
MMBtu
|
- | - | $(-455.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs