Assessment Year | 2017 |
---|---|
Principal Product | hardwood flooring |
NAICS | 321918: Other Millwork (including Flooring) |
SIC | 2426: Hardwood Dimension and Flooring Mills |
Sales Range | $10 M to 50M |
# of Employees | 81 |
Plant Area |
116,417
ft2
|
Annual Production | 2,900
thousand feet
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $203,233 | 2,643,539 |
kWh
|
$0.077 | |
Electricity Demand | $79,439 | 14,314 |
kW-mo/yr
|
$5.55 | |
Electricity Fees | $3,362 | - |
|
- | |
Natural Gas | $30,940 | 14,691 |
MMBtu
|
$2.11 | |
Waste Disposal Costs | |||||
Water Usage | $1,218 | 71 |
Tgal
|
$17.09 | |
Water Disposal | $3,463 | 71 |
Tgal
|
$48.60 | |
TOTAL YEARLY COSTS | $321,655 | ||||
RECOMMENDED SAVINGS* | $48,250 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $23,388 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $9,343 | $2,478 | - | - |
$9,343
-
MMBtu
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,922 | $41,392 |
$6,225
80,955
kWh
|
$2,697
-
kW-mo/yr
|
- | - | - | - | |
03 | 4.642: Install sensors to detect and avoid jams | $6,579 | $1,611 |
$5,985
77,834
kWh
|
$594
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,331 | - |
$4,416
57,420
kWh
|
$1,915
-
kW-mo/yr
|
- | - | - | - | |
05 | 3.4151: Minimize water usage | $4,164 | $750 | - | - | - |
$1,218
-
Tgal
|
$3,463
-
Tgal
|
$(-517.0) | |
06 | 2.4157: Establish a predictive maintenance program | $3,443 | $1,000 |
$3,657
47,555
kWh
|
$1,582
-
kW-mo/yr
|
- | - | - | $(-1,796.0) | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,545 | $8,388 |
$2,195
28,541
kWh
|
$350
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.4224: Upgrade controls on compressors | $2,479 | $10,000 |
$1,730
22,502
kWh
|
$749
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.7241: Install outside air damper / economizer on hvac unit | $1,157 | $3,278 |
$807
10,500
kWh
|
$350
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.4239: Eliminate or reduce compressed air usage | $1,140 | $1,058 |
$796
10,350
kWh
|
$344
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.4151: Develop a repair/replace policy | $1,024 | $699 |
$869
11,303
kWh
|
$377
-
kW-mo/yr
|
- | - | - | $(-222.0) | |
12 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $863 | $431 |
$602
7,833
kWh
|
$261
-
kW-mo/yr
|
- | - | - | - | |
13 | 2.1233: Analyze flue gas for proper air/fuel ratio | $260 | $850 | - | - |
$260
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $48,250 | $71,935 |
$27,282
354,793
kWh
|
$9,219
-
kW-mo/yr
|
$9,603
-
MMBtu
|
$1,218
-
Tgal
|
$3,463
-
Tgal
|
$(-2,535.0) | ||
TOTAL IMPLEMENTED | $23,388 | $52,760 |
$17,964
233,607
kWh
|
$7,182
-
kW-mo/yr
|
$260
-
MMBtu
|
- | - | $(-2,018.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs