Assessment Year 2008
Principal Product Electrical Connectors
NAICS 334417: Electronic Connector Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range $10
M
to 50
M
# of Employees 33
Plant Area 131,069
ft2
Annual Production 300,000
pieces
Production Hrs. Annual 6,110
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $116,296 2,654,107
kWh
Electricity Demand $56,309 7,519
kW-mo/yr
Electricity Fees $4,958 -
Natural Gas $102,393 12,340
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $56,191 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $55,207

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $12,171 $21,771 $8,763
199,987
kWh
$3,408
-
kW-mo/yr
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $11,887 $23,022 $8,659
197,600
kWh
$3,228
-
kW-mo/yr
-
03 2.2136: Install / repair insulation on steam lines $7,524 $5,130 $2,876
65,632
kWh
- $4,648
-
MMBtu
04 2.3191: Use demand controller or load shedder $4,524 $8,800 - $4,524
-
kW-mo/yr
-
05 2.2414: Use waste heat from hot flue gases to preheat $3,611 $7,140 - - $3,611
-
MMBtu
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $3,318 - $2,709
61,812
kWh
$609
-
kW-mo/yr
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $2,345 - $1,708
38,978
kWh
$637
-
kW-mo/yr
-
08 2.4157: Establish a predictive maintenance program $2,621 $425 $2,142
48,888
kWh
$479
-
kW-mo/yr
-
09 2.4151: Develop a repair/replace policy $1,750 $1,363 $1,428
32,590
kWh
$322
-
kW-mo/yr
-
10 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,750 $387 $1,428
32,590
kWh
$322
-
kW-mo/yr
-
11 2.4235: Remove or close off unneeded compressed air lines $1,649 - $1,259
28,730
kWh
$390
-
kW-mo/yr
-
12 2.4231: Reduce the pressure of compressed air to the minimum required $984 $52 $729
16,645
kWh
$255
-
kW-mo/yr
-
13 2.1233: Analyze flue gas for proper air/fuel ratio $963 $1,431 - - $963
-
MMBtu
14 2.4221: Install compressor air intakes in coolest locations $610 $196 $453
10,349
kWh
$157
-
kW-mo/yr
-
15 2.4239: Eliminate or reduce compressed air usage $484 $200 $394
8,986
kWh
$90
-
kW-mo/yr
-
TOTAL RECOMMENDED $56,191 $69,917 $32,548
742,787
kWh
$14,421
-
kW-mo/yr
$9,222
-
MMBtu
TOTAL IMPLEMENTED $55,207 $69,865 $31,819
726,142
kWh
$14,166
-
kW-mo/yr
$9,222
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs