Assessment Year | 1998 |
---|---|
Principal Product | Nylon Plastic Pellets |
NAICS |
n/a
|
SIC | 2299: Textile goods, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 89 |
Plant Area |
196,000
ft2
|
Annual Production | 50,000,000
lb
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $690,476 | 18,715,710 |
kWh
|
$0.037 |
Electricity Demand | $264,624 | 30,916 |
kW-mo/yr
|
$8.56 |
Electricity Fees | $14,442 | - |
|
- |
Natural Gas | $7,179 | 1,260 |
MMBtu
|
$5.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $69,348 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,561 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Other Gas Savings | Water Disposal Savings | Solid Waste (haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $1,704 | $708 | - |
$1,704
-
MMBtu
|
- | - | - | - | |
02 | 2.7241: Install outside air damper / economizer on hvac unit | $3,108 | $4,432 |
$3,108
136,577
kWh
|
- | - | - | - | - | |
03 | 2.1331: Burn a less expensive grade of fuel | $8,776 | $10,800 | - | - |
$8,776
-
MMBtu
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $2,575 | $289 | - |
$2,575
-
MMBtu
|
- | - | - | - | |
05 | 2.2511: Insulate bare equipment | $24,472 | $4,450 | - |
$24,472
-
MMBtu
|
- | - | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,598 | $1,280 |
$1,598
49,238
kWh
|
- | - | - | - | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $712 | $670 |
$712
4,689
kWh
|
- | - | - | - | - | |
08 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $75 | - | - | - | - | - |
$75
-
lb
|
- | |
09 | 3.3131: Use evaporation to concentrate material | $20,520 | $23,298 | - | - | - |
$20,520
-
Tgal
|
- | - | |
10 | 4.422: Utilize outside contracting | $5,808 | - | - | - | - | - | - | $5,808 | |
TOTAL RECOMMENDED | $69,348 | $45,927 |
$5,418
190,504
kWh
|
$28,751
-
MMBtu
|
$8,776
-
MMBtu
|
$20,520
-
Tgal
|
$75
-
lb
|
$5,808 | ||
TOTAL IMPLEMENTED | $28,561 | $7,108 |
$2,310
53,927
kWh
|
$26,176
-
MMBtu
|
- | - |
$75
-
lb
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Other Gas Savings | Water Disposal Savings | Solid Waste (haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs