Assessment Year | 1996 |
---|---|
Principal Product | Blow Molding Products |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 280 |
Plant Area |
300,000
ft2
|
Annual Production | 125,000
ton
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $487,012 | 19,839,684 |
kWh
|
$0.025 |
Electricity Demand | $272,380 | 35,778 |
kW-mo/yr
|
$7.61 |
Electricity Fees | $83,584 | - |
|
- |
Natural Gas | $8,641 | 1,383 |
MMBtu
|
$6.25 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $270,381 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $257,196 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,489 | $2,245 |
$4,638
109,027
kWh
|
$851
-
kW-mo/yr
|
- | - | |
02 | 2.4133: Use most efficient type of electric motors | $4,473 | $6,759 |
$2,430
57,151
kWh
|
$2,043
-
kW-mo/yr
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,954 | $1,800 |
$6,954
163,834
kWh
|
- | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $3,197 | $224 |
$3,197
75,322
kWh
|
- | - | - | |
05 | 2.2511: Insulate bare equipment | $180 | $520 |
$180
4,103
kWh
|
- | - | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $240,100 | $11,700 |
$236,223
4,431,419
kWh
|
$3,877
-
kW-mo/yr
|
- | - | |
07 | 3.5217: Reuse / recycle/ sell paper products | $9,988 | $10,000 |
$(-12.0)
(-293)
kWh
|
- | $(-600.0) | $10,600 | |
TOTAL RECOMMENDED | $270,381 | $33,248 |
$253,610
4,840,563
kWh
|
$6,771
-
kW-mo/yr
|
$(-600.0) | $10,600 | ||
TOTAL IMPLEMENTED | $257,196 | $23,024 |
$250,425
4,765,534
kWh
|
$6,771
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs