Assessment Year | 1994 |
---|---|
Principal Product | Transducers, Regulators and Diaphragms |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 275 |
Plant Area |
160,000
ft2
|
Annual Production | 9,000,000
pieces
|
Production Hrs. Annual | 5,200
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $324,214 | 4,996,483 |
kWh
|
$0.065 |
Natural Gas | $96,440 | 19,590 |
MMBtu
|
$4.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,575 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,678 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,087 | $1,173 |
$1,087
38,101
kWh
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $461 | $14,040 |
$461
16,120
kWh
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $475 | $300 |
$475
16,706
kWh
|
- | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $279 | - |
$279
9,672
kWh
|
- | |
05 | 2.7444: Close holes and openings in building such as broken windows | $4,413 | $340 | - |
$4,413
-
MMBtu
|
|
06 | 2.2511: Insulate bare equipment | $12,889 | $3,360 | - |
$12,889
-
MMBtu
|
|
07 | 2.2136: Install / repair insulation on steam lines | $192 | $15 | - |
$192
-
MMBtu
|
|
08 | 2.4221: Install compressor air intakes in coolest locations | $216 | $303 |
$43
1,465
kWh
|
$173
-
MMBtu
|
|
09 | 2.6212: Turn off equipment during breaks, reduce operating time | $11,134 | $4,830 |
$1,605
64,771
kWh
|
$9,529
-
MMBtu
|
|
10 | 2.1213: Direct warmest air to combustion intake | $207 | - |
$140
4,982
kWh
|
$67
-
MMBtu
|
|
11 | 2.6242: Minimize operation of equipment maintained in standby condition | $227 | - |
$227
7,913
kWh
|
- | |
12 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $995 | $260 | - |
$995
-
MMBtu
|
|
TOTAL RECOMMENDED | $32,575 | $24,621 |
$4,317
159,730
kWh
|
$28,258
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,678 | $2,051 |
$2,251
78,839
kWh
|
$1,427
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs