Assessment Year | 2015 |
---|---|
Principal Product | Juice Energy Products |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
460,000
ft2
|
Annual Production | 178,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $770,961 | 14,325,944 |
kWh
|
$0.054 |
Electricity Demand | $262,765 | 27,230 |
kW-mo/yr
|
$9.65 |
Natural Gas | $410,735 | 85,088 |
MMBtu
|
$4.83 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $237,191 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $117,364 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $8,390 | $2,440 | - | - | - |
$8,390
-
MMBtu
|
|
02 | 2.4322: Use or replace with energy efficient substitutes | $42,177 | $162,050 |
$21,936
406,213
kWh
|
$20,242
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $25,309 | $1,250 |
$25,309
468,679
kWh
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,605 | $6,953 |
$1,737
32,175
kWh
|
$868
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $70,459 | $247,939 |
$56,637
1,048,834
kWh
|
$13,822
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,664 | $8,092 |
$1,664
30,807
kWh
|
- | - | - | |
07 | 2.7261: Install timers and/or thermostats | $2,710 | $2,471 |
$1,882
34,843
kWh
|
- | - |
$829
-
MMBtu
|
|
08 | 2.2135: Repair and eliminate steam leaks | $18,886 | $375 | - | - | - |
$18,886
-
MMBtu
|
|
09 | 2.1233: Analyze flue gas for proper air/fuel ratio | $53,631 | $44,000 | - | - | - |
$53,631
-
MMBtu
|
|
10 | 2.2511: Insulate bare equipment | $317 | $46 | - | - | - |
$317
-
MMBtu
|
|
11 | 2.3212: Optimize plant power factor | $11,042 | $47,988 | - | - | $11,042 | - | |
TOTAL RECOMMENDED | $237,191 | $523,604 |
$109,164
2,021,551
kWh
|
$34,932
-
kW-mo/yr
|
$11,042 |
$82,054
-
MMBtu
|
||
TOTAL IMPLEMENTED | $117,364 | $252,035 |
$83,828
1,552,356
kWh
|
$13,822
-
kW-mo/yr
|
- |
$19,715
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs