Assessment Year | 1994 |
---|---|
Principal Product | Lumber Products |
NAICS |
n/a
|
SIC | 2499: Wood Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
50,000
ft2
|
Annual Production | 7,800
thousand feet
|
Production Hrs. Annual | 5,600
hrs
|
Location (State) | West Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $265,130 | 4,802,169 |
kWh
|
$0.055 |
Wood | $1,012,554 | 2,531,384 |
MMBtu
|
$0.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $96,788 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,768 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Wood Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,696 | $6,825 |
$2,696
63,013
kWh
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $939 | $30,260 |
$939
21,981
kWh
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $451 | $245 |
$451
10,551
kWh
|
- | |
04 | 2.2511: Insulate bare equipment | $170 | $78 | - |
$170
-
MMBtu
|
|
05 | 2.1213: Direct warmest air to combustion intake | $81,860 | $2,875 | - |
$81,860
-
MMBtu
|
|
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,801 | - |
$3,801
88,804
kWh
|
- | |
07 | 2.2136: Install / repair insulation on steam lines | $1,775 | $2,457 | - |
$1,775
-
MMBtu
|
|
08 | 2.2511: Insulate bare equipment | $128 | $180 | - |
$128
-
MMBtu
|
|
09 | 2.2511: Insulate bare equipment | $194 | $200 | - |
$194
-
MMBtu
|
|
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,844 | $10 |
$2,844
66,530
kWh
|
- | |
11 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,570 | $1,360 | - |
$1,570
-
MMBtu
|
|
12 | 2.4314: Use synthetic lubricant | $360 | - |
$360
8,499
kWh
|
- | |
TOTAL RECOMMENDED | $96,788 | $44,490 |
$11,091
259,378
kWh
|
$85,697
-
MMBtu
|
||
TOTAL IMPLEMENTED | $10,768 | $37,275 |
$10,640
248,827
kWh
|
$128
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Wood Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs