Assessment Year 2023
Principal Product Cheese and Dry Whey product
NAICS 311513: Cheese Manufacturing
SIC 2022: Natural, Processed, and Imitation Cheese
Sales Range $50
M
to 100
M
# of Employees 400
Plant Area 320,000
ft2
Annual Production 277,000,000
lb
Production Hrs. Annual 7,280
hrs
Location (State) Wisconsin

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $2,617,355 51,017,315
kWh
Electricity Demand $807,537 83,596
kW-mo/yr
Electricity Fees $173,452 -
Natural Gas $2,254,017 662,623
MMBtu
TOTAL YEARLY COSTS $5,852,361
RECOMMENDED SAVINGS* $55,671 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $43,430

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.4314: Use synthetic lubricant $16,641 $45,000 $12,699
247,542
kWh
$3,942
-
kW-mo/yr
-
02 2.3132: Recharge batteries on during off-peak demand periods $13,369 $10,160 - - $13,369
03 2.4111: Utilize energy-efficient belts and other improved mechanisms $8,320 $13,750 $6,349
123,771
kWh
$1,971
-
kW-mo/yr
-
04 2.4221: Install compressor air intakes in coolest locations $7,070 $1,900 $4,530
88,298
kWh
$2,541
-
kW-mo/yr
-
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,171 $17,500 $3,946
76,916
kWh
$1,225
-
kW-mo/yr
-
06 2.7221: Lower temperature during the winter season and vice-versa $5,100 - $3,815
74,374
kWh
$1,285
-
kW-mo/yr
-
TOTAL RECOMMENDED $55,671 $88,310 $31,339
610,901
kWh
$10,963
-
kW-mo/yr
$13,369
TOTAL IMPLEMENTED $43,430 $68,910 $22,864
445,687
kWh
$7,197
-
kW-mo/yr
$13,369
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs