Assessment Year | 2023 |
---|---|
Principal Product | Transportation Refrigeration Units, and R&D |
NAICS | 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen |
SIC | 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
535,000
ft2
|
Annual Production | 600,000
units
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Minnesota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $389,753 | 6,335,048 |
kWh
|
$0.062 | |
Electricity Demand | $192,225 | 16,762 |
kW-mo/yr
|
$11.47 | |
Electricity Fees | $138,392 | - |
|
- | |
Natural Gas | $287,218 | 34,429 |
MMBtu
|
$8.34 | |
Waste Disposal Costs | |||||
Water Usage | $37,442 | 2,795 |
Tgal
|
$13.40 | |
Water Disposal | $13,975 | 2,795 |
Tgal
|
$5.00 | |
TOTAL YEARLY COSTS | $1,059,005 | ||||
RECOMMENDED SAVINGS* | $45,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $19,115 | $49,375 | - |
$19,115
-
kW-mo/yr
|
- | - | - | |
02 | 3.4116: Meter recycled water (to reduce sewer charges) | $9,760 | $1,950 | - | - | - | - |
$9,760
-
Tgal
|
|
03 | 2.3132: Recharge batteries on during off-peak demand periods | $8,477 | $12,900 | - | - | $8,477 | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,991 | $4,800 |
$1,436
23,167
kWh
|
$555
-
kW-mo/yr
|
- | - | - | |
05 | 2.7229: Air condition only space necessary | $1,770 | - | - | - | - |
$1,770
-
MMBtu
|
- | |
06 | 2.4239: Eliminate or reduce compressed air usage | $1,580 | - |
$1,139
18,374
kWh
|
$440
-
kW-mo/yr
|
- | - | - | |
07 | 2.7444: Close holes and openings in building such as broken windows | $808 | $680 | - | - | - |
$808
-
MMBtu
|
- | |
08 | 2.4221: Install compressor air intakes in coolest locations | $799 | $2,886 |
$576
9,294
kWh
|
$222
-
kW-mo/yr
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $744 | $320 |
$537
8,656
kWh
|
$208
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $45,044 | $72,911 |
$3,688
59,491
kWh
|
$20,540
-
kW-mo/yr
|
$8,477 |
$2,578
-
MMBtu
|
$9,760
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs