Assessment Year | 2021 |
---|---|
Principal Product | Industrial Food Service Manufacturing & Assembly |
NAICS | 333318: Other Commercial and Service Industry Machinery Manufacturing |
SIC | 3589: Service Industry Machinery, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 400 |
Plant Area |
350,000
ft2
|
Annual Production | 3,000
pieces
|
Production Hrs. Annual | 6,032
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $253,513 | 3,954,750 |
kWh
|
$0.064 | |
Electricity Demand | $88,813 | 11,446 |
kW-mo/yr
|
$7.76 | |
Electricity Fees | $11,932 | - |
|
- | |
Natural Gas | $75,809 | 26,285 |
MMBtu
|
$2.88 | |
Waste Disposal Costs | |||||
Water Usage | $19,684 | 1,897 |
Tgal
|
$10.37 | |
TOTAL YEARLY COSTS | $449,751 | ||||
RECOMMENDED SAVINGS* | $40,877 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $27,233 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,833 | $15,082 |
$7,552
117,982
kWh
|
$5,281
-
kW-mo/yr
|
- | |
02 | 2.7224: Reduce space conditioning during non-working hours | $10,941 | - | - | - |
$10,941
-
MMBtu
|
|
03 | 2.7232: Replace existing hvac unit with high efficiency model | $6,669 | $37,278 | - | - |
$6,669
-
MMBtu
|
|
04 | 2.5196: Use small number of high output units instead of many small inefficient units | $3,750 | $6,000 |
$2,404
37,565
kWh
|
$1,346
-
kW-mo/yr
|
- | |
05 | 2.7224: Reduce space conditioning during non-working hours | $2,618 | - |
$2,618
40,908
kWh
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,850 | $4,250 |
$1,491
23,294
kWh
|
$359
-
kW-mo/yr
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $942 | $1,650 |
$826
12,883
kWh
|
$116
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $642 | $1,890 |
$550
8,576
kWh
|
$92
-
kW-mo/yr
|
- | |
09 | 2.6127: Maintain air filters by cleaning or replacement | $433 | $1,490 |
$365
5,704
kWh
|
$68
-
kW-mo/yr
|
- | |
10 | 2.7444: Close holes and openings in building such as broken windows | $199 | $750 | - | - |
$199
-
MMBtu
|
|
TOTAL RECOMMENDED | $40,877 | $68,390 |
$15,806
246,912
kWh
|
$7,262
-
kW-mo/yr
|
$17,809
-
MMBtu
|
||
TOTAL IMPLEMENTED | $27,233 | $17,722 |
$10,720
167,466
kWh
|
$5,373
-
kW-mo/yr
|
$11,140
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs