| Assessment Year | 2025 |
|---|---|
| Principal Product | Roasted Coffee |
| NAICS | 311920: Coffee and Tea Manufacturing |
| SIC | 2095: Roasted Coffee |
| Sales Range | less than $500 k |
| # of Employees | 140 |
| Plant Area |
98,000
ft2
|
| Annual Production | 35,000
lb
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $333,519 | 2,719,435 |
kWh
|
$0.12 |
| Electricity Demand | $33,595 | 6,485 |
kW-mo/yr
|
$5.18 |
| Electricity Fees | $4,462 | - |
|
- |
| Natural Gas | $307,006 | 48,490 |
MMBtu
|
$6.33 |
| TOTAL YEARLY COSTS | $678,582 | |||
| RECOMMENDED SAVINGS* | $74,447 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $2,602 | - |
$2,371
19,280
kWh
|
$231
-
kW-mo/yr
|
- | |
| 02 | 2.7314: Reduce ventilation air | $4,684 | $1,500 | - | - |
$4,684
-
MMBtu
|
|
| 03 | 2.2443: Re-use or recycle hot or cold process exhaust air | $28,847 | $27,000 |
$4,956
40,294
kWh
|
$483
-
kW-mo/yr
|
$23,408
-
MMBtu
|
|
| 04 | 2.4224: Upgrade controls on compressors | $8,172 | $9,000 | - | - |
$8,172
-
MMBtu
|
|
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,540 | $1,500 |
$14,160
115,122
kWh
|
$1,380
-
kW-mo/yr
|
- | |
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,945 | $9,000 |
$12,708
103,320
kWh
|
$1,237
-
kW-mo/yr
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $657 | $1,000 |
$620
5,040
kWh
|
$37
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $74,447 | $49,000 |
$34,815
283,056
kWh
|
$3,368
-
kW-mo/yr
|
$36,264
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs