Assessment Year | 2018 |
---|---|
Principal Product | Stair Lifts |
NAICS | 333921: Elevator and Moving Stairway Manufacturing |
SIC | 3534: Elevators and Moving Stairways |
Sales Range | $100 M to 500M |
# of Employees | 334 |
Plant Area |
75,000
ft2
|
Annual Production | 9,700
units
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $206,740 | 2,856,190 |
kWh
|
$0.072 | |
Electricity Demand | $68,927 | 7,702 |
kW-mo/yr
|
$8.95 | |
Electricity Fees | $28,863 | - |
|
- | |
Natural Gas | $34,657 | 5,662 |
MMBtu
|
$6.12 | |
Waste Disposal Costs | |||||
Water Usage | $11,757 | 1,364 |
Tgal
|
$8.62 | |
TOTAL YEARLY COSTS | $350,944 | ||||
RECOMMENDED SAVINGS* | $80,646 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $48,274 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,391 | $22,752 |
$19,698
272,180
kWh
|
$6,693
-
kW-mo/yr
|
- | |
02 | 2.9114: Use solar heat to make electricty | $20,855 | $48,500 |
$20,855
276,867
kWh
|
- | - | |
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $9,244 | $6,840 | - | - |
$9,244
-
MMBtu
|
|
04 | 2.4239: Eliminate or reduce compressed air usage | $9,118 | $19,300 |
$9,118
125,970
kWh
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,496 | $2,000 |
$6,011
83,034
kWh
|
$1,485
-
kW-mo/yr
|
- | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $2,084 | - |
$1,610
22,241
kWh
|
$474
-
kW-mo/yr
|
- | |
07 | 2.7231: Use radiant heater for spot heating | $1,744 | $5,250 | - | - |
$1,744
-
MMBtu
|
|
08 | 2.7446: Utilize sensors controlling roof and wall openings | $1,291 | $533 | - | - |
$1,291
-
MMBtu
|
|
09 | 2.4221: Install compressor air intakes in coolest locations | $804 | $1,172 |
$554
7,585
kWh
|
$250
-
kW-mo/yr
|
- | |
10 | 2.7135: Install occupancy sensors | $765 | $600 |
$765
10,574
kWh
|
- | - | |
11 | 2.7447: Install vinyl strip / high speed / air curtain doors | $637 | $740 | - | - |
$637
-
MMBtu
|
|
12 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $217 | $200 |
$163
2,266
kWh
|
$54
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $80,646 | $107,887 |
$58,774
800,717
kWh
|
$8,956
-
kW-mo/yr
|
$12,916
-
MMBtu
|
||
TOTAL IMPLEMENTED | $48,274 | $51,214 |
$36,991
511,010
kWh
|
$8,902
-
kW-mo/yr
|
$2,381
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs