Assessment Year | 2005 |
---|---|
Principal Product | Paper board cartons |
NAICS | 322212: Folding Paperboard Box Manufacturing |
SIC | 2657: Folding Paperboard Boxes, Including Sanitary |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
110,000
ft2
|
Annual Production | 12,000
ton
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $91,451 | 3,024,300 |
kWh
|
$0.030 |
Electricity Demand | $50,806 | 8,208 |
kW-mo/yr
|
$6.19 |
Electricity Fees | $18,166 | - |
|
- |
Natural Gas | $36,488 | 4,965 |
MMBtu
|
$7.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,299 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,479 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,442 | $32,548 |
$7,409
232,260
kWh
|
$3,033
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,838 | $14,420 |
$5,838
183,002
kWh
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,926 | $3,443 |
$4,046
126,820
kWh
|
$1,880
-
kW-mo/yr
|
- | |
04 | 2.4224: Upgrade controls on compressors | $3,641 | $7,095 |
$3,641
114,138
kWh
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,866 | $1,720 |
$1,195
37,447
kWh
|
$671
-
kW-mo/yr
|
- | |
06 | 2.7261: Install timers and/or thermostats | $842 | $1,200 | - | - |
$842
-
MMBtu
|
|
07 | 2.3132: Recharge batteries on during off-peak demand periods | $390 | $800 | - |
$390
-
kW-mo/yr
|
- | |
08 | 2.7135: Install occupancy sensors | $354 | $840 |
$354
11,101
kWh
|
- | - | |
TOTAL RECOMMENDED | $29,299 | $62,066 |
$22,483
704,768
kWh
|
$5,974
-
kW-mo/yr
|
$842
-
MMBtu
|
||
TOTAL IMPLEMENTED | $9,479 | $21,515 |
$9,479
297,140
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs