| Assessment Year | 2002 |
|---|---|
| Principal Product | Newspaper |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $10 M to 50M |
| # of Employees | 110 |
| Plant Area |
33,000
ft2
|
| Annual Production | 4,680,000
pieces
|
| Production Hrs. Annual | 5,300
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $38,712 | 1,193,760 |
kWh
|
$0.032 |
| Electricity Demand | $38,621 | 3,726 |
kW-mo/yr
|
$10.37 |
| Electricity Fees | $7,949 | - |
|
- |
| Natural Gas | $21,921 | 2,715 |
MMBtu
|
$8.07 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $10,916 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,436 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 3.7137: Replace cloth rags with paper towels | $4,113 | - | - | - | - | $4,113 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,187 | $8,714 |
$1,222
35,825
kWh
|
$965
-
kW-mo/yr
|
- | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,916 | $150 |
$1,522
44,624
kWh
|
$394
-
kW-mo/yr
|
- | - | |
| 04 | 2.6231: Utilize controls to operate equipment only when needed | $1,333 | - |
$745
21,840
kWh
|
$588
-
kW-mo/yr
|
- | - | |
| 05 | 2.7243: Improve air circulation with destratification fans / other methods | $797 | $800 |
$(-50.0)
(-1,360)
kWh
|
- |
$847
-
MMBtu
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $327 | $640 |
$251
7,358
kWh
|
$76
-
kW-mo/yr
|
- | - | |
| 07 | 2.7135: Install occupancy sensors | $243 | $1,000 |
$120
3,511
kWh
|
$123
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $10,916 | $11,304 |
$3,810
111,798
kWh
|
$2,146
-
kW-mo/yr
|
$847
-
MMBtu
|
$4,113 | ||
| TOTAL IMPLEMENTED | $5,436 | $8,864 |
$3,489
102,289
kWh
|
$1,947
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs