Assessment Year | 1996 |
---|---|
Principal Product | Plastic Shampoo Bottles |
NAICS |
n/a
|
SIC | 3085: Plastics Bottles |
Sales Range | $5 M to 10M |
# of Employees | 100 |
Plant Area |
106,000
ft2
|
Annual Production | 0
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $302,035 | 5,087,046 |
kWh
|
$0.059 |
Electricity Demand | $102,038 | 8,372 |
kW-mo/yr
|
$12.19 |
Electricity Fees | $10,752 | - |
|
- |
Natural Gas | $23,592 | 6,580 |
MMBtu
|
$3.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,250 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,745 | $1,950 |
$7,914
137,749
kWh
|
$831
-
kW-mo/yr
|
- | - | - | |
02 | 2.2621: Modify refrigeration system to operate at a lower pressure | $5,104 | - |
$4,413
71,512
kWh
|
$691
-
kW-mo/yr
|
- | - | - | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $2,583 | - | - | - |
$2,583
-
MMBtu
|
- | - | |
04 | 2.7261: Install timers and/or thermostats | $267 | $400 | - | - |
$267
-
MMBtu
|
- | - | |
05 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $2,400 | - | - | - | - | - |
$2,400
-
lb
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $2,631 | $740 |
$2,308
42,497
kWh
|
$323
-
kW-mo/yr
|
- | - | - | |
07 | 3.8133: Convert to aqueous cleaning | $1,850 | $4,500 | - | - | - |
$1,850
-
gal
|
- | |
08 | 2.3132: Recharge batteries on during off-peak demand periods | $1,701 | - | - |
$1,701
-
kW-mo/yr
|
- | - | - | |
09 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,415 | $500 | - | - |
$1,415
-
MMBtu
|
- | - | |
10 | 2.3134: Shift from daytime to nighttime operation | $353 | - | - |
$353
-
kW-mo/yr
|
- | - | - | |
11 | 2.7241: Install outside air damper / economizer on hvac unit | $201 | $700 |
$201
5,275
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $27,250 | $8,790 |
$14,836
257,033
kWh
|
$3,899
-
kW-mo/yr
|
$4,265
-
MMBtu
|
$1,850
-
gal
|
$2,400
-
lb
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs