Assessment Year 2014
Principal Product Portable pneumatic power tools
NAICS 333991: Power-Driven Handtool Manufacturing
SIC 3546: Power-Driven Handtools
Sales Range $50
M
to 100
M
# of Employees 175
Plant Area 150,000
ft2
Annual Production 155,000
pieces
Production Hrs. Annual 2,080
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $72,891 1,227,900
kWh
Electricity Demand $54,643 4,976
kW-mo/yr
Electricity Fees $7,365 -
Natural Gas $36,235 4,605
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $40,088 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $25,520

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.8121: Apply for tax-free status for energy purchases $5,498 - - - - $5,498
02 2.4322: Use or replace with energy efficient substitutes $3,063 - $1,416
24,000
kWh
$1,647
-
kW-mo/yr
- -
03 2.4231: Reduce the pressure of compressed air to the minimum required $1,600 - $1,600
27,115
kWh
- - -
04 3.1161: Eliminate/reduce an operation $405 - $323
5,475
kWh
$82
-
kW-mo/yr
- -
05 2.7111: Reduce illumination to minimum necessary levels $2,925 $846 $1,410
23,903
kWh
$1,515
-
kW-mo/yr
- -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,627 $979 $396
6,710
kWh
$101
-
kW-mo/yr
- $1,130
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $496 $335 $496
8,400
kWh
- - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $14,974 $15,880 $6,167
104,526
kWh
$7,137
-
kW-mo/yr
- $1,670
09 2.2414: Use waste heat from hot flue gases to preheat $7,618 $15,784 - - $7,618
-
MMBtu
-
10 2.6211: Conserve energy by efficient use of vending machines $179 $562 $179
3,031
kWh
- - -
11 3.1161: Eliminate/reduce an operation $1,703 $5,670 $(-1,115.0)
(-18,900)
kWh
$(-1,976.0)
-
kW-mo/yr
- $4,794
TOTAL RECOMMENDED $40,088 $40,056 $10,872
184,260
kWh
$8,506
-
kW-mo/yr
$7,618
-
MMBtu
$13,092
TOTAL IMPLEMENTED $25,520 $18,040 $8,469
143,539
kWh
$8,753
-
kW-mo/yr
- $8,298
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs