ITAC Assessment: WI0190
ITAC logo
ITAC Assessment: WI0190
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1993
Principal Product Steel & wood shelving, storage
NAICS
n/a
SIC 2542: Office and Store Fixtures, Partitions, Shelving, and Lockers, Except Wood
Sales Range $10
M
to 50
M
# of Employees 152
Plant Area 300,000
ft2
Annual Production 0
units
Production Hrs. Annual 4,375
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $369,629 3,938,453
kWh
Natural Gas $82,864 28,906
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $49,419 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $36,537

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.7224: Reduce space conditioning during non-working hours $21,567 $800 - $21,567
-
MMBtu
02 2.1233: Analyze flue gas for proper air/fuel ratio $5,245 $500 - $5,245
-
MMBtu
03 2.2426: Use waste heat from flue gases to heat space conditioning air $1,049 $500 - $1,049
-
MMBtu
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $3,315 $1,186 $3,315
35,463
kWh
-
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,254 - $1,254
13,482
kWh
-
06 2.7442: Keep doors and windows shut when not on use $3,164 $500 - $3,164
-
MMBtu
07 2.7447: Install vinyl strip / high speed / air curtain doors $1,859 $8,800 - $1,859
-
MMBtu
08 2.2511: Insulate bare equipment $1,329 $96 $1,329
14,068
kWh
-
09 2.7142: Utilize higher efficiency lamps and/or ballasts $2,892 $2,909 $2,892
30,774
kWh
-
10 2.7111: Reduce illumination to minimum necessary levels $2,495 $450 $2,495
26,671
kWh
-
11 2.7135: Install occupancy sensors $1,165 $225 $1,165
12,309
kWh
-
12 2.7447: Install vinyl strip / high speed / air curtain doors $1,537 $2,200 - $1,537
-
MMBtu
13 2.4221: Install compressor air intakes in coolest locations $2,124 $320 $2,124
22,567
kWh
-
14 2.7241: Install outside air damper / economizer on hvac unit $424 $1,400 $424
4,396
kWh
-
TOTAL RECOMMENDED $49,419 $19,886 $14,998
159,730
kWh
$34,421
-
MMBtu
TOTAL IMPLEMENTED $36,537 $5,704 $8,676
92,321
kWh
$27,861
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs