Assessment Year | 1993 |
---|---|
Principal Product | Printing on Plastics |
NAICS |
n/a
|
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
85,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 6,800
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $234,827 | 4,557,737 |
kWh
|
$0.052 |
Natural Gas | $59,388 | 25,889 |
MMBtu
|
$2.29 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,301 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,491 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7226: Use computer programs to optimize hvac performance | $9,676 | $16,000 |
$9,676
187,866
kWh
|
- | |
02 | 2.7135: Install occupancy sensors | $14,825 | $24,000 |
$14,825
415,006
kWh
|
- | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $1,897 | $525 |
$1,897
36,928
kWh
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $990 | - |
$990
-
kWh
|
- | |
05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $678 | $640 |
$678
13,189
kWh
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $476 | $700 | - |
$476
-
MMBtu
|
|
07 | 2.2511: Insulate bare equipment | $148 | - |
$148
2,931
kWh
|
- | |
08 | 2.2511: Insulate bare equipment | $611 | $360 | - |
$611
-
MMBtu
|
|
TOTAL RECOMMENDED | $29,301 | $42,225 |
$28,214
655,920
kWh
|
$1,087
-
MMBtu
|
||
TOTAL IMPLEMENTED | $25,491 | $40,000 |
$25,491
602,872
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs