| Assessment Year | 1992 |
|---|---|
| Principal Product | ELECTRICAL PRODUCTS |
| NAICS |
n/a
|
| SIC | 3643: Current-Carrying Wiring Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 200 |
| Plant Area |
n/a
|
| Annual Production | 2,000,000
pieces
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | Illinois |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $195,523 | 2,699,883 |
kWh
|
$0.072 |
| Natural Gas | $13,603 | 3,885 |
MMBtu
|
$3.50 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $65,510 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $33,712 | $160,000 | n/a |
$38,597
327,374
kWh
|
$(-4,885.0)
-
MMBtu
|
- |
| 02 | 2.7261: Install timers and/or thermostats | $6,762 | $1,000 | n/a | - |
$6,762
-
MMBtu
|
- |
| 03 | 2.7221: Lower temperature during the winter season and vice-versa | $5,277 | - | n/a |
$5,277
72,978
kWh
|
- | - |
| 04 | 2.7229: Air condition only space necessary | $5,948 | - | n/a |
$5,948
82,063
kWh
|
- | - |
| 05 | 2.7226: Use computer programs to optimize hvac performance | $4,359 | $7,700 | n/a |
$4,359
60,082
kWh
|
- | - |
| 06 | 2.3191: Use demand controller or load shedder | $4,257 | $10,000 | n/a |
$4,257
-
kWh
|
- | - |
| 07 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $4,040 | $1,000 | n/a |
$4,040
55,686
kWh
|
- | - |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $356 | $1,280 | n/a |
$356
4,982
kWh
|
- | - |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $799 | $8,758 | n/a |
$1,021
14,068
kWh
|
- | $(-222.0) |
| TOTAL RECOMMENDED | $65,510 | $189,738 |
$63,855
617,233
kWh
|
$1,877
-
MMBtu
|
$(-222.0) | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs