ITAC Assessment: WI0141
ITAC logo
ITAC Assessment: WI0141
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1992
Principal Product ENVELOPES
NAICS
n/a
SIC 2677: Envelopes
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area
n/a
Annual Production 0
units
Production Hrs. Annual 6,600
hrs
Location (State) Illinois

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $287,319 3,895,956
kWh
Natural Gas $30,530 6,351
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $30,832 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $13,318

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $5,296 $5 $5,744
77,960
kWh
- $(-448.0)
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,707 $3,964 $4,707
63,892
kWh
- -
03 2.4111: Utilize energy-efficient belts and other improved mechanisms $408 - $408
5,569
kWh
- -
04 2.7447: Install vinyl strip / high speed / air curtain doors $3,297 $1,300 - $3,297
-
MMBtu
-
05 2.7447: Install vinyl strip / high speed / air curtain doors $3,704 $2,250 - $3,704
-
MMBtu
-
06 2.3132: Recharge batteries on during off-peak demand periods $4,091 - $4,091
-
kWh
- -
07 2.6212: Turn off equipment during breaks, reduce operating time $2,811 $1,500 $2,811
38,394
kWh
- -
08 2.4221: Install compressor air intakes in coolest locations $2,137 $1,280 $2,137
29,015
kWh
- -
09 2.3131: Reschedule plant operations or reduce load to avoid peaks $2,087 - $2,887
-
kWh
- $(-800.0)
10 2.6212: Turn off equipment during breaks, reduce operating time $471 - $471
6,448
kWh
- -
11 2.4133: Use most efficient type of electric motors $1,202 $2,292 $1,202
16,413
kWh
- -
12 2.1233: Analyze flue gas for proper air/fuel ratio $305 $500 - $305
-
MMBtu
-
13 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available $316 $200 $316
4,396
kWh
- -
TOTAL RECOMMENDED $30,832 $13,291 $24,774
242,087
kWh
$7,306
-
MMBtu
$(-1,248.0)
TOTAL IMPLEMENTED $13,318 $9,806 $6,317
85,874
kWh
$7,001
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs