| Assessment Year | 1990 |
|---|---|
| Principal Product | ALUMINUM CANS |
| NAICS |
n/a
|
| SIC | 3411: Metal Cans |
| Sales Range | $10 M to 50M |
| # of Employees | 240 |
| Plant Area |
n/a
|
| Annual Production | 975,000,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $733,432 | 19,977,726 |
kWh
|
$0.037 |
| Natural Gas | $434,048 | 124,328 |
MMBtu
|
$3.49 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $13,317 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,761 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $317 | $500 | - |
$367
-
MMBtu
|
$(-50.0) | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,226 | $8,680 |
$4,226
115,182
kWh
|
- | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $634 | $1,350 |
$634
17,292
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,208 | $1,224 |
$1,208
33,411
kWh
|
- | - | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $1,605 | - | - |
$1,605
-
MMBtu
|
- | |
| 06 | 2.6232: Install set-back timers | $1,304 | $1,000 |
$1,304
35,463
kWh
|
- | - | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,254 | - |
$1,254
34,291
kWh
|
- | - | |
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,065 | $750 | - |
$1,065
-
MMBtu
|
- | |
| 09 | 2.7224: Reduce space conditioning during non-working hours | $1,274 | $500 | - |
$1,274
-
MMBtu
|
- | |
| 10 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $342 | $509 | - |
$342
-
MMBtu
|
- | |
| 11 | 2.6214: Shut off pilots in standby equipment | $88 | - | - |
$88
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $13,317 | $14,513 |
$8,626
235,639
kWh
|
$4,741
-
MMBtu
|
$(-50.0) | ||
| TOTAL IMPLEMENTED | $7,761 | $11,254 |
$6,068
165,885
kWh
|
$1,693
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs